Unit installation
803 C – 01/05 A – pag. 11/17
Screw compressors
The newest Stargate
TM
single-screw compressor has a well balanced compression mechanism which cancels the
screw rotor load in both the radial and axial directions. Inherent to the basic single-screw compressor design is the
virtually load-free operation, that gives main bearing design life of 3-4 times greater than twin-screws, and
eliminates expensive and complicated thrust balancing schemes. The two exactly opposed gaterotors create two
exactly opposed compression cycles. Compression is made at the lower and upper parts of the screw rotor at the
same time, thus cancelling the radial loads. Also, both ends of the screw rotor are subjected to suction pressure
only, which cancels the axial loads and eliminates the huge thrust loads inherent in twin-screw compressors.
Oil injection is used for these compressors in order to get high COP at high condensing pressure. PFS units are
provided with an high efficiency oil separator to maximise oil extraction.
Compressors have a infinitely variable capacity control down to 25% of its total capacity. This control is made by
means of capacity slides controlled by microprocessors.
Standard start is star-delta type; Soft start type is available (as option) in order to have lower inrush current.
Standard controls
High pressure control
The high pressure switch will shut-down the compressor when the discharge pressure exceeds the setting point
value.
Warning: during testing, stand by the emergency stop switch on control panel, to shut the unit down should the
safety control malfunction. Be sure that the installed gauge is accurately adjusted.
Phase/voltage monitor
The phase/voltage monitor is a device which provides protection against three-phase electrical motor loss due to
power failure conditions, phase loss, and phase reversal. Whenever any of these conditions occur, a contact
opens to the microprocessor which then de-energizes all inputs. When proper power is restored, contacts close
and microprocessor enables compressors for operation. When three-phase power has been applied, the output
relay should close and the "run light" should come on. If the output relay does not close, perform the following
tests:
1. Check the voltages between L1-L2, L1-L3 and L2-L3 (L1, L2, L3 are the three phases). These voltages should
be approximately equal and within + 10% of the rated three-phase line-to-line voltage.
2. If these voltages are extremely low or widely unbalanced check the power system to determine the cause of the
problem.
3. If the voltages are good, using a phase tester, verify that phases are in A, B, C sequence for L1, L2 and L3.
Correct rotation is required for compressor operation. If required to do so by phase sequence, turn off the
power and interchange any two of the supply power leads at the disconnect. This may be necessary as the
phase voltage monitor is sensitive to phase reversal. Turn on the power. The output relay should now close
after the appropriate delay.
System Maintenance
General
To ensure proper operation at peak capacity and to avoid damage to package components, a program of periodic
inspections should be set up and followed. The following items are intended as a guide and are to be used during
inspection and must be combined with sound refrigeration and electrical practicies to ensure trouble-free
performance. The liquid line sightglass indicator on all circuits must be checked to be sure the glass is full and
clear. If the indicator shows that a wet condition exists or if bubbles show in the glass, even with a full refrigerant
charge, the filter-drier element must be changed.