Product manual

4 McQuay IM 782-4
Introduction
Receiving and Handling
1 Carefully check items against the bills of lading to verify
all crates and cartons were received. Carefully inspect all
units for damage when received. Report visible and
concealed damage immediately to the carrier and a file a
claim for damage.
2 Destiny air handler units are thoroughly inspected before
leaving the factory. Install units carefully to prevent
damage.
3 Leave enough space around the unit for proper
maintenance, filter removal, lubrication, belt adjustment,
and removal of coils, if necessary (refer to Figure 2 for
service clearances).
4 Use flexible connections on the inlet and outlet duct
connections of the unit.
5 For 002 - 010 sized ceiling hung units, spring isolation of
the cabinet is recommended.
6 All fans are dynamically balanced before leaving the
factory. Carefully inspect fans for rough handling that
can cause misalignment or a damaged shaft.
7 Adequately pitch and trap drain line from drain pan
connection.
Storing the Unit
Store unit on a level surface. If air handling units are to be
stored for any period of time, it is important to rotate the fan
wheel (quarterly, as a minimum) to prevent permanent
distortion of drive components. Keep the fan bearings
lubricated. Grease may settle in the lower part of the bearing,
which may lead to oxidation on the upper portion of the
bearing surface.
Store units indoors in a clean, dry environment on a level
surface. Moisture, debris, and minerals can cause permanent
damage to the cabinet and components. Do not allow
coverings to trap moisture on the galvanized surface.