Product manual
McQuay IM 782-4 33
Performance Data
Drain Pan Data
Electric Heat Data
Table 21: Drain Pan Connections
Standard
and optional
stainless
steel
Unit size
002 003 004 005 007 010 015 020 025 030
Arrangement Sloped Sloped Sloped Sloped Sloped Sloped Sloped Sloped Sloped Sloped
Connection size
- Main
1" ID MPT 1" ID MPT 1" ID MPT 1" ID MPT 1" ID MPT 1" ID MPT
1-1/4" ID
MPT
1-1/4" ID
MPT
1-1/4" ID
MPT
1-1/4" ID
MPT
Connection size
- Secondary
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
1/2" ID
MPT
Table 22: Electric Heat Data for Unit Sizes
Unit size Voltage Phase
kW Offering
1 Stage 2 Stages 3 Stages 4 Stages
002
120 1 1.5 - 4.5 4 - 9 NA NA
240 1 1.5 - 9 4 - 10 NA NA
240 3 1.5 - 10 4 - 10 NA NA
480 3 1.5 - 10 4 - 10 NA NA
600 3 1.5 - 10 4 - 10 NA NA
003
120 1 2.5 - 4.5 4 - 9 10 -13 14 - 18
240 1 2.5 - 9 4 - 18 15 - 20 20
240 3 2.5 - 15 4 - 20 15 - 20 20
480 3 2.5 - 20 4 - 20 15 - 20 20
600 3 2.5 - 20 4 - 20 15 - 20 20
004
120 1 2.5 - 4.5 4 - 9 10 -13 14 - 18
240 1 2.5 - 9 4 - 18 15 - 20 20
240 3 2.5 - 15 4 - 20 15 - 20 20
480 3 2.5 - 20 4 - 20 15 - 20 20
600 3 2.5 - 20 4 - 20 15 - 20 20
005
120 1 4 - 4.5 4 - 9 10 -13 14 - 18
240 1 4 - 9 4 - 18 15 - 26 20 - 26
240 3 4 - 15 4 - 26 15 - 26 20 - 26
480 3 4 - 26 4 - 26 15 - 26 20 - 26
600 3 4 - 26 4 - 26 15 - 26 20 - 26
007
120 1 NA 6 - 9 10 -13 14 - 18
240 1 6 - 9 6 - 18 15 - 26 20 - 36
240 3 6 - 15 6 - 30 15 - 38 20 - 38
480 3 6 - 30 6 - 38 15 - 38 20 - 38
600 3 6 - 38 6 - 38 15 - 38 20 - 38
010
120 1 NA 6 - 9 10 -13 14 - 18
240 1 6 - 9 6 - 18 15 - 26 20 - 36
240 3 6 - 15 6 - 30 15 - 45 20 - 55
480 3 6 - 30 6 - 55 15 - 55 20 - 55
600 3 6 - 38 6 - 55 15 - 55 20 - 55