Unit installation

24 IM 736-4
Section Parameter Value (Range)/Definition Initial Value/Note
MS/TP
MAC address 0-127/Media Access Control
Address (unique hardware address)
of the BACnet Communication
Module.
1/See the BAS systems integrator.
This value must be entered as a
hexadecimal value. See Appendix
A: Hexadecimal Conversion on
page 26.
Max Masters Maximum Number of Master
Controllers currently on the
network that the BACnet
Communication Module can poll.
127 Master Controllers/ See the
BAS system integrator. BAS
integrators can decrease this value
to improve network performance.
Max Info Frames Maximum Number of Information
Frames the BACnet
Communication Module can send
before it must pass the token.
5 Frames
Baudrate 9600 bps, 19200 bps, and
38400 bps/Data Transmission rate
on the MS/TP network
38400 bps/ See the BAS system
integrator. Be sure to set the
Switch to the correct position.*
*Although 76800 bps selectable, it is not a valid speed.