Specifications

76 Catalog WSC/WDC-4
Marine Water Boxes (WDC)
2 and 4 Pass Cond. (Except 18 in. 2 Pass)
Cover
Thickness
“C”
“A”
“B”
“F”
Evap. And Cond. 1 Pass
Nozzle Flanges
Are Optional
“D”
.50
2 and 4 Pass Cond. (Except 18 in. 2 Pass)
Nozzle Flanges
Are Optional
Nozzle Flanges
Are Optional
All 2 Pass Evap. - All 3 Pass Cond.
18 in. 2 Pass Cond.
“D”
.50
“D”
“E”
“E”
.50
“E”
“E”
FIGURE 2FIGURE 1
FIGURE 4FIGURE 3
Notes: 1. Evaporator connections are front facing only.
2. Condenser connections are rear facing only.
Outline Dimensions Connections
D E Pipe Size For Passes
Shell
O.D.
Vessel
A B C
Fig 2 Fig 3 Fig 4 Fig 3 Fig 4
F
Cover
Thick-
ness
1P 2P 3P 4P
Evap 5 13.00 14.00 14.50 - - - - - 22.50 - - - - - 6.94 15.00
16
Cond 5 13.00 14.00 14.50 16.50 22.50 4.35 6.94 15.00
1.00 8 5 4 4
Evap 7 17.25 18.00 22.50 - - - - - 22.50 - - - - - 7.94 19.25
18
Cond 7 17.25 18.00 16.50 - - - - - 22.50 - - - - - 7.06 19.25
1.25 8 6 5 4
20 Evap 7 17.25 18.00 22.50 - - - - - 22.50 - - - - - 7.88 19.25 1.25 8 6 5 4
Evap 8 19.50 20.00 22.50 - - - - - 22.50 - - - - - 10.12 21.50
22
Cond 8 19.50 20.00 22.50 22.50 22.50 5.62 9.93 21.50
1.50 10 8 6 5
Evap 8 19.50 20.00 22.50 - - - - - 22.50 - - - - - 11.69 21.50
26
Cond 8 19.50 20.00 22.50 22.50 22.50 7.07 11.69 21.50
1.50 10 8 8 6
Evap 12 27.75 28.00 24.50 - - - - - 24.50 - - - - - 13.62 29.75
30
Cond 12 27.75 28.00 27.50 27.50 27.50 8.12 13.00 29.75
1.75 14 10 8 8
Evap 12 28.00 28.00 27.50 - - - - - 27.50 - - - - - 16.50 30.00
36
Cond 12 28.00 28.00 27.50 27.50 27.50 9.75 16.33 30.00
2.00 16 12 10 8
Evap 13 30.50 30.00 27.50 - - - - - 35.50 - - - - - 19.38 33.00
42
Cond 13 30.50 30.00 27.50 27.50 27.50 11.63 11.63 33.00
2.00 20 16 12 10
Evap - - - - - - - - 36.00 36.00 - - - - - 40.00 - - - - - 22.64 39.25
48
Cond - - - - - - - - 36.00 36.00 36.00 - - - - - 11.50 - - - - - 39.25
2.75 - - - 18 - - - - - -
Notes: See notes on previous page.