Specifications
Catalog WSC/WDC-4  65 
Condenser 
With positive pressure systems, the pressure variance with temperature is always predictable, and 
the vessel design and relief protection are based upon pure refrigerant characteristics. Negative 
pressure systems are not ASME designed, inspected and stamped. R-134a requires ASME vessel 
design, inspection and testing and uses spring-loaded pressure relief valves. Negative pressure 
units use rupture disks. When an over pressure condition occurs, the rupture disk is permanently 
destroyed. Spring-loaded relief valves purge only the amount of refrigerant required to reduce the 
system pressure to the valve setting level and then close. 
Refrigerant side design pressure is 200 psi (1380 kPa) on WSC units and 225 psi (1552 kPa) on 
WDC units. Standard water side design pressure is 150 psi (1034 kPa) on all vessels.  300 psi 
(2068 kPa) is available as an option. 
Pumpdown 
To facilitate compressor service, all McQuay centrifugal chillers are designed to permit 
pumpdown and isolation of the entire refrigerant charge in the unit’s condenser. Dual compressor 
units, and single compressor units equipped with the optional suction shutoff valve, can also be 
pumped down into the evaporator. No separate pumpout receiver is required on most 
installations. 
Table 11, Condenser Physical Data 
Condenser 
Code 
WSC WDC 
Pumpdown 
Capacity 
 lb (kg) 
Water 
Volume 
 gal (L) 
Vessel Dry 
Weight 
lb (kg) 
Number 
of Relief 
Valves 
Add for 
MWB 
lb (kg) 
MWB Cover 
Only, 
Weight 
lb (kg) 
C1609  X    468 (213)  24 (92)  1589 (718)  2  283 (128)  81 (37) 
C1612  X    677 (307)  33 (123)  1870 (847)  2  283 (128)  81 (37) 
C1809  X    597 (271)  34 (128)  1835 (831)  2  402 (182)  124 (56) 
C1812  X    845 (384)  44 (166)  2183 (989)  2  402 (182)  124 (56) 
C2009  X    728 (330)  47 (147)  2230 (1010)  2  478 (216)  148 (67) 
C2012  X    971 (440)  62 (236)  2677 (1213)  2  478 (216)  148 (67) 
C2209  X    822 (372)  60 (228)  2511 (1137)  2  478 (216)  148 (67) 
C2212  X    1183 (537)  76 (290)  3031 (1373)  2  478 (216)  148 (67) 
C2212    X  1110 (504)  89 (337)  3075 (1395)  2  478 (216)  148 (67) 
C2216    X  1489 (676)  114 (430)  3861 (1751)  2  478 (216)  148 (67) 
C2416    X  1760 (799)  143 (540)  4647 (2188)  2  685 (310)  230 (104) 
C2609  X    1242 (563)  89 (335)  3210 (1454)  2  902 (408)  302 (137) 
C2612  X    1656 (751)  111 (419)  3900 (1767)  2  902 (408)  302 (137) 
C2616    X  2083 (945)  159 (603)  5346 (2425)  2  902 (408)  302 (137) 
C3009  X    1611 (731)  114 (433)  4356 (1973)  2  1420 (643)  517 (234) 
C3012  X    2148 (975)  144 (545)  5333 (2416)  2  1420 (643)  517 (234) 
C3016    X  2789 (1265)  207 (782)  6752 (3063)  4  1420 (643)  517 (234) 
C3612  X    2963 (1344)  234 (884)  7508 (3401)  2  2115 (958)  805 (364) 
C3616    X  3703 (1725)  331 (1251)  9575 (4343)  4  2115 (958)  805 (364) 
C4212  X    3796 (1722)  344 (1302)  10267 (4651)  2  2836 (1285)  1181 (535) 
C4216    X  5010 (2273)  475 (1797)  12662 (5743)  4  2836 (1285)  1181 (535) 
C4220    X  5499 (2494)  634 (2401)  17164 (7785)  4  2836 (1285)  1181 (535) 
C4812  X    4912 (2228)  491 (1855)  13077 (5924)  4  4578 (2074)  1837 (8320 
C4816    X  5581 (2532)  717 (2715)  18807 (8530)  4  4578 (2074)  1837 (8320 
C4820    X  7034 (3191)  862 (3265)  23106 (10481)  4  4578 (2074)  1837 (8320 
Notes: 
1.  Condenser pumpdown capacity based on 90% full at 90°F. 
2.  Vessel weight includes the shell, maximum tubes, and standard heads, no refrigerant. 
3.  MWB, marine water box, weight add is the water box weight minus a standard dished head weight. 
Compressor 
Table 12, Compressor Weights 
Compressor Size  
048/050 063 079 087 100 113 126 
Weight lb (kg)  
870 
 (390) 
3200 
(1440) 
3200 
(1440) 
3200 
(1440) 
6000 
(2700) 
6000 
(2700) 
6000 
(2700) 