Specifications

Catalog WSC/WDC-4 47
Refrigerant Monitors
Detects all halogen based refrigerants Continuous digital display of system status
Optional analog output for remote monitoring System malfunction detection and indication
Visual alarm indication Can sample up to 250 feet (76 meters) away
Fresh air inlet for automatic re-zeroing Multi-unit capability in a single monitor
ETL listed UL STD 3101-1 and CAN/CSA 1010.1
MODELS
Model RM-1 1 Zone Monitor
Model RM-4 4 Zone Monitor
Model RM-8 8 Zone Monitor
Model RM-16 16 Zone Model
SPECIFICATIONS
Sensitivity: As low as 1 PPM Range: 0 to 1000 PPM Weight: 25 lbs. (11 kg)
Power: 120/240 Volt, 50/60 Hz
Operating Environment: 32°F-125°F
Size: W=16.5in. D=6.75in. H=15in.
Alarm Trip Points (Percent of Full Scale): Low Alarm=0 to 100, Main Alarm=0 to 100, High Alarm=100
Alarm Outputs: Indicator Light, Alarm Relays, RS232 Computer Interface
OPTIONS and ACCESSORIES
Analog Output, 4-20 ma (RMA-AO) Remote Strobe Light, 120 V (RMA-L)
Remote Horn, 120V (RMA-H) Remote Light and Horn Set (RMA-LH)
Plastic Pick-up Tubing, ¼ inch OD, 250 ft. Reel (RMA-T) Diaphragm Pump (RMA-P) *
Course Replacement Filter (RMA-CF) * 5 Micron Replacement Filter (RMA-F) *
(*) Replacement parts. Original pump and filters are shipped with unit.