Specifications

Catalog WSC/WDC-4 45
Refrigerant Recovery Units
Although McQuay chillers can pump the entire refrigerant charge into the condenser and valve it off, there
are occasions when pumpout units are required, due purely to specification requirements or unusual job
considerations.
McQuay offers two sizes of refrigerant recovery units (Model RRU) and one recovery unit that is factory
mounted on a storage vessel (Model PRU). Recovery units are ETL listed. Capacities for R-22 are ARI
certified. The storage tank is designed, constructed and stamped in accordance with ASME standards.
Model RRU Refrigerant Recovery Units
Size and Specifications
Model
(1) R-22 Liquid
Transfer Rate
lb/m (kg/m)
(1) R 22 Vapor
Transfer Rate
lb/m (kg/m)
Comp.
HP
(2) Chiller
Tons (kW)
Weight
lbs (kg)
Dimensions
L x W x H
Inch (cm)
Electrical
RRU134-5 55 (25) 1.56 (0.71) 1.5 300 (1050) 115 (52) 21 x 14 x 19 (53 x 36 x 68) 1/50-60/110-115
RRU134-3 55 (25) 1.56 (0.71) 1.5 300 (1050) 115 (52) 21 x 14 x 19 (53 x 36 x 68) 1/50-60/220-230
RRU570-3 325 (148) 6.0 (2.7) 3 1000 (3500) 190 (86) 26 x 25 45 (66 x 63 x 114) 1/50-60/220-230
RRU570-V 325 (148) 6.0 (2.7) 3 1000 (3500) 190 (86) 26 x 25 45 (66 x 63 x 114) 3/50-60/220-230
RRU570-R 325 (148) 6.0 (2.7) 3 1000 (3500) 190 (86) 26 x 25 45 (66 x 63 x 114) 3/50-60/360-460
RRU570-D 325 (148) 6.0 (2.7) 3 1000 (3500) 190 (86) 26 x 25 45 (66 x 63 x 114) 3/60/575
NOTES:
1. Transfer rate for R-22 is ARI certified. R-134a capacity is given below in each unit's description.
2. Suggested maximum chiller capacity.
Refrigerant Compatibility
Units are suitable for use with the following refrigerants normally found on McQuay chillers; R-12, R-22, R-
134a, R-410A, and R-500.
Standard Equipment
Model
Equipment
RRU134 RRU570
Power Cord X X
Filter-Driers (2) 30 cu. in. (1) 48 cu. in
Electromechanical Control X X
Hoses (4) 10 ft. (1) 10 ft + (2) 20 ft
Reducing Fittings X
12 ft. Tank Float Switch Cable X
Connection Sizes ½ in. Flare ¾ in. Flare
Model RRU134
Large 1 ½-HP open drive compressor, ½-inch lines, two-point
vapor extraction and oversized air-cooled condenser speed
recovery on smaller size chillers. Purging and switching from
liquid to vapor recovery only involves turning 3-way valves-
no switching of hoses is necessary. Capacity with R-134a is
55 lb/min liquid, 1.34 lb/min vapor.