Specifications

Catalog WSC/WDC-4 39
Motor Controllers
Motor Starters
McQuay has a wide variety of starter types and options to fit virtually all applications. The
specifics of the final selection of size, enclosure, and options are covered in the catalog
PM
Starters
. Please consult the local McQuay sales office or the starter catalog for starter details.
This section contains a general overview only.
Mounting Options, Low Voltage, 200 to 600 Volts
Factory-mounted; starters furnished, mounted and wired in the factory. Due to shipping width
limitations, the starters for WSC 100 through 126 are shipped loose with cable kits and mounting
brackets for field installation and connection on the units by others.
Freestanding
; furnished by McQuay and drop shipped to the job site for setting and wiring by
others.
Starters by others
; starters furnished by others must meet McQuay Specification R35999901,
available from the local McQuay sales office. The starters are furnished and installed by others.
Table 4, Starter Mounting Arrangements
Size
Factory-
Mounted
Free-
Standing
Brackets &
Cables
WSC/WDC 050-087 X X
WSC 100-126 X X
WDC 100-126 X
Mounting Options, Medium Voltage, 2300 to 6000 Volts
All starter types in these voltages are for field setting and wiring only.
Starter Types and Descriptions
Solid state starters are available for both low and medium voltages and are similar in construction
and features regardless of voltage.
For low voltage application, Wye-Delta Closed Transition starters are available, in addition to
solid state.
For medium voltage application, autotransformer, primary reactor reduced voltage and across-the-
line starters are offered in addition to solid state.
Variable Frequency Drives (VFD)
VFDs are available on all McQuay chillers including up to 2500 tons. The fact that the larger
chillers have dual compressors allows the VFD option at a reasonable price.