Specifications
22 Catalog WSC/WDC-4
Table 1, Typical Data Point Availability
Typical Data Points
1
(W = Write, R = Read)
Active Setpoint R Cond EWT R Evap Water Pump Status R
Actual Capacity R Cond Flow Switch Status R Heat Recovery EWT R
Capacity Limit Output R Cond LWT R Heat Recovery LWT R
Capacity Limit Setpoint W Cond Pump Run Hours R Heat Setpoint W
Chiller Enable W Cond Refrigerant Pressure R
2
Ice Setpoint W
Chiller Limited R Cond Sat. Refrigerant Temp R
2
Liquid Line Refrigerant Pressure
Chiller Local/Remote R Cond Water Pump Status R Liquid Line Refrigerant Temp R
Chiller Mode Output R Cool Setpoint W Maximum Send Time W
Chiller Mode Setpoint W Current Alarm R Minimum Send Time W
Chiller On/Off R Default Values W Network Clear Alarm W
Chiller Status R Evap EWT R Oil Feed Pressure R
Compressor Discharge Temp R Evap Flow Switch Status R Oil Feed Temp R
Compressor Percent RLA R Evap LWT for Unit R Oil Sump Pressure R
Compressor Run Hours R Evap LWT for Compressor R Oil Sump Temp R
Compressor Select W Evap Pump Run Hours R Outdoor Air Temp
Compressor Starts R Evap Refrigerant Pressure R2 Pump Select W
Compressor Suction Line Temp R Evap Sat. Refrigerant Temp R2 Run Enabled R
Notes:
1. Data points available are dependent upon options selected
2. Per compressor
Figure 7, Sample System Architecture
Building Automation
System of Your Choice!
Alerton, Automated Logic, Delta Controls,
Honeywell, Invensys, Johnson Controls,
Siemens, TAC … And more
MicroTech II Centrifugal Chiller
Field Level Devices by Others
MicroTech II Unit Ventilators
VAV Boxes by Others
System
Control
Panel
Lighting
Control Panel
by Others
MicroTech II
Air Cooled Chiller
Open standard
protocol network
such as LonTalk,
Modbus or BACnet.