Operating instructions

IMM AGSB-60 47
Solid State Starter Settings
Operating Parameters Settings for Default Value and Settable Range:
No. Operating Parameter
Default Range of Setting
P1 Motor Full Load Amps (FLA) 250A 1 to 350A
P2 Motor Rated Load Amps (RLA) 1A 1 to 350A
P3 Initial Motor Starting Current 225% 100 – 350%
P4 Max. Motor Starting Current 300% 200 – 350%
P5 Motor Ramp Time 7 sec 2 – 10 sec
P6 Motor Stall Time 10 sec 5 – 10 sec
P7 Deceleration Level 1 28% 40 – 100%
P8 Deceleration Level 2 10% 0 – 20%
P9 Deceleration Time 2 sec Off, 1 – 10 sec
P10 Overcurrent Trip Level 140% 140%
P11 Overcurrent Trip Time 2 sec Off, 1 – 15 sec
P12 Undercurrent Trip Level 25% 25% - 100%
P13 Undercurrent Trip Time Off Off, 1 – 15 sec
P14 Motor Current Imbalance 15% 5, 10, 15, 20%
P15 Current Transformer Ratio 460V/575V 2.64 RSD Standard
P16 Meter Mode 10 RSD Standard
P17 Meter Dwell Time 2 Off, 2 – 30 sec
P18 Passcode Off
0 to 255 (enable), Off
(disable)
P19 Kick Start Off On, Off
P20 Auto Reset Capability Off On, Off