Operating instructions
38 IMM AGSB-60
Table 28, AGS 230B–AGS 475B, Wiring Information with Multiple-Point
WIRING TO UNIT POWER BLOCK
TERMINAL SIZE (AMPS) CONNECTOR WIRE RANGE PER PHASE (COPPER WIRE ONLY)
AGS
UNIT
SIZE
VOLTS HZ
CKT 1 CKT 2 CKT 3 CKT 1 CKT 2 CKT 3
460
230
575
60 400 400 --
#6-350 #6-350 --
460
250
575
60 400 400 --
#6-350 #6-350 --
460
270
575
60 400 400 --
#6-350 #6-350 --
460
300
575
60 400 400 --
#6-350 #6-350 --
460
320
575
60 400 400 --
#6-350 #6-350 --
460
340
575
60 400 400 400
#6-350 #6-350 #6-350
460
370
575
60 400 400 400
#6-350 #6-350 #6-350
460
400
575
60 400 400 400
#6-350 #6-350 #6-350
460
420
575
60 400 400 400
#6-350 #6-350 #6-350
460
440
575
60 400 400 400
#6-350 #6-350 #6-350
460
450
575
60 400 400 400
#6-350 #6-350 #6-350
460
475
575
60 400 400 400
#6-350 #6-350 #6-350
Notes:
1. Terminal size amps are the maximum amps that the power block is rated for.
2. Complete electrical notes are on page 39.
Table 29, AGS 230B–AGS 475B, Wiring Information with Multiple-Point
WIRING TO UNIT DISCONNECT SWITCH
TERMINAL SIZE (AMPS) CONNECTOR WIRE RANGE PER PHASE (COPPER WIRE ONLY)
AGS
UNIT
SIZE
VOLTS HZ
CKT 1 CKT 2 CKT 3 CKT 1 CKT 2 CKT 3
460
230
575
60 400 400 - 3/0 - 500 3/0 - 500 -
460
250
575
60 400 400 - 3/0 - 500 3/0 - 500 -
460
270
575
60 400 400 - 3/0 - 500 3/0 - 500 -
460
300
575
60 400 400 - 3/0 - 500 3/0 - 500 -
460
320
575
60 400 400 - 3/0 - 500 3/0 - 500 -
460
340
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500
460
370
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500
460
400
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500
460
420
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500
460
440
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500
460
450
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500
460
475
575
60 400 400 400 3/0 - 500 3/0 - 500 3/0 - 500