Operating instructions

36 IMM AGSB-60
Table 25, AGS 340B–AGS 475B, Electrical Data, Standard Multiple-Point, (Circuits # 1 & 2)
ELECTRICAL CIRCUIT 1 (COMP 1) ELECTRICAL CIRCUIT 2 (COMP 2)
POWER SUPPLY FIELD FUSING POWER SUPPLY FIELD FUSING
FIELD WIRE
HUB
(Conduit
Connection)
FIELD WIRE
HUB
(Conduit
Connection)
AGS
UNIT
SIZE
VOLTS HZ
MIN.
CIRCUIT
AMPS
(MCA)
QTY
WIRE
GAUGE
QTY
HUB
SIZE
REC
FUSE
SIZE
MAX
FUSE
SIZE
MIN.
CIRCUIT
AMPS
(MCA)
QTY
WIRE
GAUGE
QTY
HUB
SIZE
REC.
FUSE
SIZE
MAX.
FUSE
SIZE
460
262 6 3/0 (3) 1 3.0 350 450 262 6 3/0 (3) 1 3.0 350 450
340
575
60
230 3 250 1 2.5 300 400 230 3 250 1 2.5 300 400
460
262 6 3/0 (3) 1 3.0 350 450 262 6 3/0 (3) 1 3.0 350 450
370
575
60
230 3 250 1 2.5 300 400 230 3 250 1 2.5 300 400
460
262 6 3/0 (3) 1 3.0 350 450 306 6 3/0 1 3.0 400 500
400
575
60
230 3 250 1 2.5 300 400 260 6 3/0 (3) 1 3.0 350 400
460
306 6 3/0 1 3.0 400 500 306 6 3/0 1 3.0 400 500
420
575
60
260 6 3/0 (3) 1 3.0 350 400 260 6 3/0 (3) 1 3.0 350 400
460
306 6 3/0 1 3.0 400 500 306 6 3/0 1 3.0 400 500
440
575
60
260 6 3/0 (3) 1 3.0 350 400 260 6 3/0 (3) 1 3.0 350 400
460
306 6 3/0 1 3.0 400 500 337 6 4/0 1 3.0 450 500
450
575
60
260 6 3/0 (3) 1 3.0 350 400 285 6 3/0 1 3.0 350 450
460
337 6 4/0 1 3.0 450 500 337 6 4/0 1 3.0 450 500
475
575
60
285 6 3/0 1 3.0 350 450 285 6 3/0 1 3.0 350 450
Notes:
1. Table based on 75°C field wire.
2. Complete electrical notes are on page 39.
3. 3/0 wire is required for the disconnect switch option, 2/0 can be used for power block connection.
Table 25, Electrical Data, AGS 340B – 475B, (Circuit #3)
ELECTRICAL CIRCUIT 3 (COMP 3)
POWER SUPPLY FIELD FUSING
FIELD WIRE
HUB
(Conduit
Connection)
AGS
UNIT
SIZE
VOLTS HZ
MINIMUM
CIRCUIT
AMPS
(MCA)
QTY
WIRE
GAUGE
QTY
HUB
SIZE
REC.
FUSE
SIZE
MAX.
FUSE
SIZE
460 262 6 3/0 (3) 1 3.0 350 450
340
575
60
230 3 250 1 2.5 300 400
460 306 6 3/0 1 3.0 400 500
370
575
60
260 6 3/0 (3) 1 3.0 350 400
460 306 6 3/0 1 3.0 400 500
400
575
60
260 6 3/0 (3) 1 3.0 350 400
460 306 6 3/0 1 3.0 400 500
420
575
60
260 6 3/0 (3) 1 3.0 350 400
460 337 6 4/0 1 3.0 450 500
440
575
60
285 6 3/0 1 3.0 350 450
460 337 6 4/0 1 3.0 450 500
450
575
60
285 6 3/0 1 3.0 350 450
460 337 6 4/0 1 3.0 450 500
475
575
60
285 6 3/0 1 3.0 350 450
Notes:
1. Table based on 75°C field wire.
2. Complete electrical notes are on page 39.
3. 3/0 wire is required for the disconnect switch option, 2/0 can be used for power block connection.