Operating instructions
IMM AGSB-60 35
Table 23, AGS 230B – AGS 475B, Electrical Data, Optional Single-Point
POWER SUPPLY
FIELD WIRE
HUB
(Conduit Connection)
FIELD FUSE SIZE or
HACR BREAKER SIZE
AGS
UNIT
SIZE
VOLTS HZ
MINIMUM
CIRCUIT
AMPACITY
(MCA)
QTY
WIRE
GAUGE
QTY
NOMINAL
SIZE (In.)
RECOM-
MENDED
MAXIMUM
460 475 6 250 2 2.5 600 600
230
575
60
418 6 4/0 2 2.0 500 500
460 519 6 300 2 3.0 600 700
250
575
60
447 6 4/0 2 2.0 500 600
460 555 6 300 2 3.0 700 700
270
575
60
471 6 250 2 2.5 600 600
460 586 6 350 2 3.0 700 800
300
575
60
496 6 250 2 2.5 600 700
460 611 6 350 2 3.0 700 800
320
575
60
516 6 300 2 3.0 600 700
460 688 12 4/0 2 3.0 800 800
340
575
60
605 12 3/0 2 3.0 700 700
460 732 12 250 2 4.0 800 800
370
575
60
634 12 3/0 2 3.0 700 800
460 768 12 250 2 4.0 800 800
400
575
60
658 12 4/0 2 3.0 800 800
460 804 12 250 2 4.0 1000 1000
420
575
60
683 12 4/0 2 3.0 800 800
460 835 12 300 2 4.0 1000 1000
440
575
60
708 12 4/0 2 3.0 800 800
460 860 12 300 2 4.0 1000 1000
450
575
60
728 12 4/0 2 3.0 800 800
460 885 12 300 2 4.0 1000 1000
475
575
60
748 12 250 2 4.0 800 800
Notes
1. Table based on 75°C field wire.
2. A “HACR” breaker is a circuit breaker designed for use on equipment with multiple motors. It stands for Heating, Air Conditioning, and Refrigeration.
3. Complete electrical notes are on page 39.
Table 24, AGS 230B – AGS 320B, Electrical Data, Standard Multiple-Point, Two-Circuit Units
ELECTRICAL CIRCUIT 1 (COMP 1) ELECTRICAL CIRCUIT 2 (COMP 2)
POWER SUPPLY FIELD FUSING POWER SUPPLY FIELD FUSING
FIELD WIRE
HUB
(Conduit
Connection)
FIELD WIRE
HUB
(Conduit
Connection)
AGS
UNIT
SIZE
VOLTS HZ
MIN.
CIRCUIT
AMPS
(MCA)
QTY
WIRE
GAUGE
QTY
HUB
SIZE
REC
FUSE
SIZE
MAX
FUSE
SIZE
MIN.
CIRCUIT
AMPS
(MCA)
QTY
WIRE
GAUGE
QTY
HUB
SIZE
REC
FUSE
SIZE
MAX
FUSE
SIZE
460
262 6 3/0 (3) 1 3.0 350 450 262 6 3/0 (3) 1 3.0 350 450
230
575
60
230 3 250 1 2.5 300 400 230 3 250 1 2.5 300 400
460
262 6 3/0 (3) 1 3.0 350 450 306 6 3/0 1 3.0 400 500
250
575
60
230 3 250 1 2.5 300 400 260 6 3/0 (3) 1 3.0 350 400
460
306 6 3/0 1 3.0 400 500 306 6 3/0 1 3.0 400 500
270
575
60
260 6 3/0 (3) 1 3.0 350 400 260 6 3/0 (3) 1 3.0 350 400
460
306 6 3/0 1 3.0 400 500 337 6 4/0 1 3.0 450 500
300
575
60
260 6 3/0 (3) 1 3.0 350 400 285 6 3/0 1 3.0 350 450
460
337 6 4/0 1 3.0 450 500 337 6 4/0 1 3.0 450 500
320
575
60
285 6 3/0 1 3.0 350 450 285 6 3/0 1 3.0 350 450
Notes:
1. Table based on 75°C field wire.
2. Complete electrical notes are on page 39.
3. 3/0 wire is required for the disconnect switch option, 2/0 can be used for power block connection.