Product manual

8 IOMM ACR/AGR-1
Table 3, AGR-AM Isolator Loads At Each Mounting Location With Copper Fins
1 2 3 4 TOTAL UNITAGR-AM
Size
lb kg lb kg lb kg lb kg lb kg
070 AM 1171 531 1476 670 1009 457 1264 574 4920 2232
075 AM 1526 692 1863 845 1142 518 1384 628 5915 2683
080 AM 1587 720 1937 879 1187 538 1439 653 6150 2790
085 AM 1634 741 1995 905 1222 554 1482 672 6334 2873
090 AM 1669 757 2038 924 1249 566 1514 687 6469 2934
095 AM 1672 758 2041 926 1250 567 1516 688 6479 2939
100 AM 1673 759 2042 926 1251 568 1517 688 6483 2941
Table 4, ACR-A Isolator Loads At Each Mounting Location With Copper Fins
1 2 3 4 TOTAL UNITACR
Size
lb kg lb kg lb kg lb kg lb kg
060 A 1025 465 1292 586 883 400 1107 502 4307 1954
065 A 1042 473 1313 596 897 407 1125 510 4377 1985
070 A 1089 494 1373 623 938 425 1176 533 4575 2075
075 A 1134 514 1430 648 977 443 1225 555 4765 2161
080 A 1526 692 1863 845 1142 518 1384 628 5915 2683
090 A 1587 720 1937 879 1187 538 1439 653 6150 2790
100 A 1669 757 2038 924 1249 566 1514 687 6469 2934
110 A 1672 758 2041 926 1250 567 1516 688 6479 2939
120 A 1673 759 2042 926 1251 568 1517 688 6483 2941
Water Piping
Local authorities can supply the installer with the proper building and safety codes required for safe
and proper installation.
Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the
following when installing water piping:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Install drains at the lowest
points in the system.
4. A means of maintaining adequate system water pressure (expansion tank or regulating valve).
5. Temperature and pressure indicators located at the unit to aid in unit servicing.
6. A strainer or other means of removing foreign matter from the water before it enters the pump.
Place the strainer far enough upstream to prevent cavitation at the pump inlet (consult pump
manufacturer for recommendations). The use of a strainer will prolong pump life and keep system
performance up.
7. Place a strainer in the water line just before the inlet of the evaporator. This will help prevent
foreign material from entering and decreasing the performance of the evaporator.
CAUTION
If separate disconnect is used for the 115V supply to the evaporator heating cable,
mark the disconnect clearly to ensure disconnect is not accidentally shut off during
cold seasons.
8. The shell-and-tube evaporator has a thermostat and heating cable to prevent freeze-up down to
-20°F (-29°C) that should be used if located in a sub-freezing location. It is suggested that the
heating cable be wired to a separate 110V supply circuit. All water piping to the unit must also be
protected to prevent freezing.