Product manual
44 IOMM ACR/AGR-1
Standard Controller Setpoints (optional Zone Terminal required to
change values)
VALUESTEMPLATE
NAME
FACTORY SETPOINT RANGE
OA/AI3 Lim SP 80°F 0 to 100°F
OA/AI3 Reset SP -40°F -100 to 100°F
LvgWtr Rband SP 0°F 0 to 15°F
Unoccpd Lvg SP 70°F 40 to 90°F
OA Lockout SP -10°F -20 to 65°F
Lvg Low Lim SP 20°F 20 to 40°F
SoftSta Capcty 50% 0 to 100%
SoftStart Time 2 min 0 to 20 minutes
Software Description (Global UNT Interface Kit required to read or
change variables)
Variable
Name
Description Default Value Range
LPSS Low Pressure Starting Setpoint 10 psi 5 to 15 psi
SLPT Starting Low Pressure Time 260 sec 90 to 300 seconds
MLPS Minimum Low Pressure Setpoint 5 psi Calculated (LPSS-LPSD) 5 psi
LPSD Low Pressure Starting Differential 5 psi 3 to 10 psi
LPFS Low Pressure Freezestat setpoint 54 psi 30 to 55 psi
LPHL Low Pressure High Limit 57 psi 40 to 60 psi
LPLL Low Pressure Low Limit 55 psi 40 to 55 psi
FSTP Freezestat Time Period 60 sec 60 seconds fixed
PDTD Pumpdown Delay Time Period 60 sec 60 seconds fixed