Product manual

IOMM ACR/AGR-1 23
AGR-AM Data
ACR Data
Table 15, 60 Hz, Single Point Power Electrical Data
POWER SUPPLY
Field Wire Conduit Hub
ACR-AS
Cond.
Unit
Model
AGR-AM
Chiller
Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
Quantity
Nominal
Size
Max. Fuse
or
HACR Breaker
Size
208 231 3 250 1 2.00 300
230 231 3 250 1 2.00 300
380 134 3 1/0 1 1.5 175
460 114 3 #2 1 1.25 150
060As
575 90 3 #3 1 1.00 125
208 237 3 250 1 2.00 300
230 237 3 250 1 2.00 300
380 137 3 1/0 1 1.50 175
460 117 3 #1 1 1.00 150
065AS
575 90 3 #3 1 1.00 125
208 271 3 300 1 2.50 350
230 258 3 300 1 2.50 350
380 150 3 1/0 1 1.50 200
460 133 3 1/0 1 1.50 175
070AS
575 98 3 #3 1 1.00 125
208 298 3 350 1 2.50 400
230 275 3 300 1 2.50 350
380 160 3 2/0 1 1.50 225
460 146 3 1/0 1 1.50 200
075AS
575 104 3 #2 1 1.25 125
208 322 3 400 1 2.50 450
230 300 3 350 1 2.50 400
380 190 3 3/0 1 2.00 250
460 153 3 2/0 1 1.50 200
070AM
575 114 3 #2 1 1.25 150
208 351 3 500 1 3.00 450
230 329 3 400 1 2.50 450
380 220 3 4/0 1 2.00 300
460 163 3 2/0 1 1.50 225
080AS 075AM
575 126 3 #1 1 1.50 150
208 384 6 3/0 2 2.00 500
230 373 3 500 1 3.00 500
380 240 3 250 1 2.50 300
460 187 3 3/0 1 2.00 250
090AS 080A
575 151 3 2/0 1 1.50 200
208 411 6 4/0 2 2.00 500
230 408 6 4/0 2 2.00 500
380 256 3 300 1 2.50 350
460 206 3 4/0 1 2.00 250
100AS 085AM
575 171 3 3/0 1 2.00 225
208 411 6 4/0 2 2.00 500
230 408 6 4/0 2 2.00 500
380 256 3 300 1 2.50 350
460 206 3 4/0 1 2.00 250
090AM
575 171 3 3/0 1 2.00 225
208 461 6 250 2 2.00 600
230 458 6 4/0 2 2.00 600
380 269 3 300 1 2.50 350
460 220 3 4/0 1 2.00 300
110AS 095AM
575 176 3 3/0 1 2.00 225
208 501 6 250 2 2.00 700
230 498 6 250 2 2.00 700
380 279 3 300 1 2.50 350
460 231 3 250 1 2.00 300
120AS 100AM
575 180 3 3/0 1 2.00 250
All Electrical Data notes are on page 26