Unit installation

IOMM ACZ/AGZ 23
Electrical Data AGZ-AM
Electrical Data ACZ
Table 11, AGZ-030AM - 050AM, ACZ 030A - 055A,
60 Hz, Single Point Power Electrical Data
Minimum POWER SUPPLY Max. Fuse
ACZ AGZ-AM Circuit Field Wire Hub or
Unit Size Unit Size Volts Ampacity Wire Nominal HACR Breaker
(MCA) Quantity Gauge Quantity Size Size
208 117 3 1 1 1.25 (32) 125
230 117 3 1 1 1.25 (32) 125
030A - 380 77 3 4 1 1.00 (25) 90
460 61 3 6 1 1.00 (25) 70
575 48 3 6 1 1.00 (25) 50
208 131 3 1/0 1 1.50 (38) 150
230 131 3 1/0 1 1.50 (38) 150
035A 030AM 380 86 3 3 1 1.25 (32) 100
460 68 3 4 1 1.00 (25) 80
575 53 3 6 1 1.00 (25) 60
208 143 3 1/0 1 1.50 (38) 150
230 143 3 1/0 1 1.50 (38) 150
040A 035AM 380 93 3 3 1 1.25 (32) 110
460 73 3 4 1 1.00 (25) 80
575 58 3 6 1 1.00 (25) 70
208 159 3 2/0 1 1.50 (38) 175
230 159 3 2/0 1 1.50 (38) 175
045A 040AM 380 111 3 2 1 1.25 (32) 125
460 78 3 4 1 1.00 (25) 90
575 67 3 4 1 1.00 (25) 80
208 183 3 3/0 1 2.00 (51) 200
230 183 3 3/0 1 2.00 (51) 200
050A 045AM 380 116 3 1 1 1.25 (32) 125
460 94 3 3 1 1.25 (32) 110
575 76 3 4 1 1.00 (25) 90
208 198 3 3/0 1 2.00 (51) 225
230 198 3 3/0 1 2.00 (51) 225
055A 050AM 380 120 3 1 1 1.25 (32) 125
460 104 3 2 1 1.25 (32) 125
575 83 3 4 1 1.00 (25) 100
All Electrical Data notes are on page 25