Operating instructions
Start-up
Pre Start-up
The unit must be inspected to see that no components became loose or damaged during shipping or
installation.
Start-Up
There should be adequate building load (at least 50 percent of the unit full load capacity) to properly
check the operation of the unit’s refrigerant circuits.
Record all operating parameters required by the “Compressorized Equipment Warranty Form”.
Return this information within 10 working days to McQuay International as instructed on the form to
register the start-up date with the McQuay Warranty Department.
1. Verify chilled water or air-flow.
2. Verify that the remote start / stop or time clock has requested the chiller to start.
3. Set the thermostat setpoint to required temperature. For AGZ-AM units, the system water
temperature must be greater than the total of the leaving water temperature setpoint plus 1/2 the
control band before the MicroTech II controller will stage on cooling. Set the Evap Delta T and
the Start Delta T as a starting point.
4. Put both pumpdown switches (PS1 and PS2) to the ON position.
5. Put system switch (S1) to ON position.
Switch Position
Switch
ON OFF
PS1, PS2,
Pumpdown
Switches
Circuit will go through the
normal pumpdown cycle and
shut off.
Circuits will operate in the
normal automatic mode
Unit will shut off immediately
without pumping down
(emergency stop)
S1, Unit will operate in the
normal automatic mode
System Switch
6. There can be a delay of 2 minutes after closing S1. The time delay is due to the compressor
inherent motor protection or the Stage Up Timer counting. This should only occur on initial
start-up or when power to the chiller has been turned off and back on. More than one
compressor will not start at the same time.
7. After the chiller has been operating for a period of time and has become stable, check the
following:
Compressor oil level. (Some scroll compressors do not have oil sight glasses)
Refrigerant sight glass for flashing.
Rotation of condenser fans.
8. Complete the “Compressorized Equipment Warranty Form”.
IMM ACZ/AGZ-4 ACZ / AGZ-BM 59