Operating instructions
Refrigerant Specialties Kit 
Required on AGZ-BM Remote Evaporator units consisting of thermal expansion valve, solenoid 
valve, sight glass and filter-drier (sealed on Models 026 to 070, replaceable core on Models 075 to 
130). 
Electrical 
Multi-Point Electrical Connection 
Provides a power connection to each of the unit’s two electrical circuits. 
Disconnect Switch with Through-the-Door Handle 
A factory or field-installed option for service use, nonfused disconnect switch (mounted inside the 
power section of the control box) with a through-the-door handle is available with single and multi-
point power supply. 
Phase Loss/Voltage Protection 
Phase loss with under/over voltage protection and multiple LED indication of fault type is available 
as a factory-installed option to guard against compressor motor burnout. 
Convenience Outlet 
10.0 amp, 115 volt outlet located in control panel to provide power for servicing unit. 
Ground Fault Protection 
Protects equipment from damage from line-to-ground fault currents less than those required for 
conductor protection. 
High Short Circuit Current Protection 
Provides control panel protection against short circuit currents per following table: 
Voltage 208 240 460 600 
Current (kA)  120  100  65  25 
High Ambient Control Panel 
Consists of exhaust fan with rain hood, two inlet screens with filters, necessary controls and wiring 
to allow operation to 125°F. The option can be factory or field-installed as a kit. Must be used for: 
•  Ambient temperatures above 105°F (40°C) with fan VFD (low ambient option) 
•  Ambient temperatures above 115°F (46°C) with standard FanTrol control. 