Operating instructions

Dimensional Data
Figure 26, Dimensions: ACZ 030B - 080B
AGZ 026BM – 070BM
100.4
(2550)
X
88.0 (2335)
25.1
(637)
43.8
(1111)
6.4 (162)
14.3 (364)
FIELD CONTROL
CONNECTION
POWER
ENTRY
POINT
0.875
KNOCK OUT
Y
Z
94.4 (2397)
9.1
(231)
16.7
424)
25.8
(656)
19.9
(506)
19.9
(507)
SUCTION
CONN.
HOT GAS
CONN.
LIQUID
CONN.
67.8 (1721)
13.3 (338)
2.0
(51)
51.2 (1301)
8.9 (226)
25.0
(636)
COMPRESSOR
CIRCUIT #1
COMPRESSOR
CIRCUIT #2
ISOLATOR LOCATIONS ON BOTTOM OF RAIL
DWG. #3305196-R03
CONTROL
PANEL
CONTROL
PANEL
13.3 (338)
SUCTION
LINE #2
SUCTION
LINE #1
HOT GAS
BYPASS #1
HOT GAS
BYPASS #2
LIQUID
LINE #1
LIQUID
LINE #2
REFRIGERANT CONNECTIONS
NOTES:
1. Hail and wind guards add 20 inches to the width of each side.
2. Be sure that the expansion valves’ sensing bulb and capillary are attached to the correct suction line.
Center of Gravity in. (mm) Weights lbs. (kg)
ACZ-B AGZ-BM Liquid
Conn.
Suction
Conn.
Unit Size Unit Size
X Y Z Shipping Operating
030B 026BM
(2) 1 3/8 (2) 2 1/8 36 (914) 42 (1067) 42 (1067) 3550 (1610) 3600 (1633)
035B 030BM
(2) 1 3/8 (2) 2 1/8 36 (914) 42 (1067) 42 (1067) 3550 (1610) 3600 (1633)
040B 035BM
(2) 1 3/8 (2) 2 1/8 36 (914) 42 (1067) 42 (1067) 3550 (1610) 3600 (1633)
045B 040BM
(2) 1 3/8 (2) 2 1/8 36 (914) 41 (1041) 41 (1041) 3550 (1610) 3610 (1637)
050B 045BM
(2) 1 3/8 (2) 2 1/8 36 (914) 41 (1041) 41 (1041) 3590 (1628) 3650 (1656)
055B 050BM
(2) 1 3/8 (2) 2 5/8 36 (914) 42 (1067) 42 (1067) 3730 (1692) 3800 (1724)
060B 055BM
(2) 1 3/8 (2) 2 5/8 35 (889) 42 (1067) 43 (1092) 3780 (1715) 3850 (1746)
065B 060BM
(2) 1 3/8 (2) 2 5/8 35 (889) 42 (1067) 43 (1092) 3820 (1733) 4040 (1833)
070B 065BM
(2) 1 3/8 (2) 2 5/8 35 (889) 43 (1092) 45 (1143) 3970 (1801) 4070 (1846)
080B 070BM
(2) 1 3/8 (2) 2 5/8 36 (914) 44 (1118) 46 (1168) 4080 (1851) 4180 (1896)
52 ACZ / AGZ-BM IMM ACZ/AGZ-4