Table 34, ACZ BC & AGZ BM Electrical Data, Single Point (Above 105°F)
Power Supply Max. Fuse
Field Wire
Recomm’d.
Fuse
Minimum
ACZ
AGZ
Circuit
Or HACR
Unit
Unit Volts
Or HACR
Wire
Ampacity
Breaker
Size
Size
Breaker
Quantity
Gauge
(MCA)
Size
Size
75C
208 378 6 250 450 450
230 362 6 4/0 400 400
380 194 3 3/0 225 225
460 187 3 3/0 225 225
090B 075B
575 145 3 1/0 175 175
208 398 6 250 450 450
230 382 6 250 450 450
380 234 3 250 250 250
460 200 3 4/0 225 225
100B 085B
575 151 3 1/0 175 175
208 416 6 300 500 500
230 414 6 300 500 500
380 270 3 300 300 300
460 211 3 4/0 250 250
110B 090B
575 157 3 2/0 175 175
208 522 6 400 600 600
230 463 6 350 500 500
380 273 3 300 300 300
460 230 3 4/0 250 250
120B 100B
575 187 3 3/0 200 200
208 612 6 -
(
2
)
350 700 700
230 528 6 - (2) 300 600 600
380 307 3 350 350 350
460 263 3 300 300 300
130B 110B
575 211 3 4/0 225 225
208 613 6 -
(
2
)
350 700 700
230 613 6 - (2) 350 700 700
380 352 6 - (2) 4/0 400 400
460 286 3 350 300 300
140B 120B
575 219 3 4/0 250 250
208 613 6 -
(
2
)
350 700 700
230 613 6 - (2) 350 700 700
380 393 6 250 450 450
460 307 3 350 350 350
155B 130B
575 228 3 250 250 250
NOTES:
1. Units operating in ambient temperatures of 95°F (35°C) and above must use the Maximum Fuse or HACR
Breaker size.
49.
2. All Electrical Data notes are on page
3. (2) in column with wire qty. indicates that two conduits are required.
4. Conduit hubs are not supplied.
46 ACZ / AGZ-BM IMM ACZ/AGZ-4