Operating instructions
IMM ACZ/AGZ-4 ACZ / AGZ-BM 45
Table 33, ACZ BC & AGZ BM Electrical Data, Multi-Point (106°F to 125°F)
Electrical Circuit #1 Electrical Circuit #2
Power Supply Power Supply
Field Wire Field Wire
ACZ
Unit
Size
AGZ
Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max. Fuse
or HACR
Breaker
Size
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max.
Fuse
or HACR
Breaker
Size
208 77 3 #4 90 100 77 3 #4 90 100
230 70 3 #4 80 90 70 3 #4 80 90
380 42 3 #8 50 50 40 3 #8 50 50
460 36 3 #8 45 45 36 3 #8 45 45
030B 026B
575 27 3 #10 35 35 27 3 #10 35 35
208 77 3 #4 90 100 88 3 #3 100 110
230 70 3 #4 80 90 81 3 #4 100 110
380 42 3 #8 50 50 50 3 #8 60 60
460 36 3 #8 45 45 42 3 #8 50 50
035B 030B
575 27 3 #10 35 35 34 3 #10 45 45
208 88 3 #3 100 110 88 3 #3 100 110
230 81 3 #4 100 110 81 3 #4 100 110
380 50 3 #8 60 60 50 3 #8 60 60
460 42 3 #8 50 50 42 3 #8 50 50
040B 035B
575 34 3 #10 45 45 34 3 #10 45 45
208 98 3 #3 125 125 98 3 #3 125 125
230 88 3 #3 110 110 88 3 #3 110 110
380 60 3 #6 70 80 60 3 #6 70 80
460 44 3 #8 50 60 44 3 #8 50 60
045B 040B
575 37 3 #8 45 50 37 3 #8 45 50
208 98 3 #3 125 125 119 3 #1 150 150
230 88 3 #3 110 110 109 3 #2 125 150
380 60 3 #6 70 80 70 3 #4 80 90
460 44 3 #8 50 60 55 3 #6 70 70
050B 045B
575 37 3 #8 45 50 45 3 #8 60 60
208 119 3 #1 150 150 119 3 #1 150 150
230 109 3 #2 125 150 109 3 #2 125 150
380 70 3 #4 80 90 70 3 #4 80 90
460 55 3 #6 70 70 55 3 #6 70 70
055B 050B
575 45 3 #8 60 60 45 3 #8 60 60
208 119 3 #1 150 150 142 3 1/0 175 200
230 109 3 #2 125 150 130 3 #1 175 175
380 70 3 #4 80 90 84 3 #4 100 110
460 55 3 #6 70 70 65 3 #4 80 90
060B 055B
575 45 3 #8 60 60 55 3 #6 70 70
208 142 3 1/0 175 200 142 3 1/0 175 200
230 130 3 #1 175 175 130 3 #1 175 175
380 84 3 #4 100 110 84 3 #4 100 110
460 65 3 #4 80 90 65 3 #4 80 90
065B 060B
575 55 3 #6 70 70 55 3 #6 70 70
208 146 3 1/0 175 200 171 3 2/0 225 225
230 134 3 1/0 175 175 161 3 2/0 200 225
380 82 3 #4 100 110 91 3 #3 110 125
460 67 3 #6 80 90 80 3 #4 100 110
070B 065B
575 55 3 #6 70 70 65 3 #6 90 90
208 171 3 2/0 225 225 171 3 2/0 225 225
230 161 3 2/0 200 225 161 3 2/0 200 225
380 91 3 #3 110 125 91 3 #3 110 125
460 80 3 #4 100 110 80 3 #4 100 110
080B 070B
575 65 3 #6 90 90 65 3 #6 90 90
Notes:
1. All Electrical Data notes are on page
49.
2. Conduit hubs are not supplied.