Operating instructions

IMM ACZ/AGZ-4 ACZ / AGZ-BM 43
Electrical Data High Ambient
Table 31, ACZ BC & AGZ BM Electrical Data, Single Point
Power Supply
Field Wire
ACZ Unit
Size
AGZ
Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Max. Fuse
Or HACR
Breaker
Size
208 147 3 1/0 175 175
230 133 3 1/0 150 150
380 80 3 #4 90 90
460 68 3 #4 80 80
030B 026B
575 53 3 #6 60 60
208 158 3 2/0 175 175
230 144 3 1/0 175 175
380 88 3 #3 100 100
460 74 3 #4 90 90
035B 030B
575 59 3 #6 70 70
208 168 3 2/0 200 200
230 155 3 2/0 175 175
380 96 3 #3 110 110
460 80 3 #4 90 90
040B 035B
575 64 3 #6 70 70
208 187 3 3/0 200 200
230 167 3 2/0 200 200
380 113 3 #2 125 125
460 84 3 #4 90 90
045B 040B
575 70 3 #4 80 80
208 207 3 4/0 225 225
230 188 3 3/0 225 225
380 123 3 #1 125 125
460 94 3 #3 110 110
050B 045B
575 78 3 #4 90 90
208 226 3 4/0 225 225
230 207 3 3/0 225 225
380 132 3 1/0 150 150
460 104 3 #2 125 125
055B 050B
575 86 3 #3 100 100
208 249 3 250 250 250
230 229 3 4/0 250 250
380 147 3 1/0 175 175
460 115 3 #2 125 125
060B 055B
575 96 3 #3 110 110
208 270 3 300 300 300
230 248 3 250 250 250
380 160 3 2/0 175 175
460 124 3 #1 150 150
065B 060B
575 105 3 #2 125 125
208 303 3 350 350 350
230 282 3 300 350 350
380 164 3 2/0 200 200
460 138 3 1/0 175 175
070B 065B
575 115 3 #2 125 125
208 323 3 400 400 400
230 304 3 350 350 350
380 172 3 2/0 200 200
460 150 3 1/0 175 175
080B 070B
575 123 3 #1 150 150
NOTES:
1. Units operating in ambient temperatures above 95°F (35°C) must use the Maximum Fuse or HACR Breaker size
2. All Electrical Data notes are on page
49.
3. Conduit hubs are not provided.