Operating instructions
IMM ACZ/AGZ-4 ACZ / AGZ-BM 41
Table 29, ACZ BC & AGZ BM Field Wiring Data
Wiring to Standard
Power Block
Wiring to Optional
Non-Fused Disconnect Switch
Terminal
Amps
Connector Wire Range
(Copper Wire Only)
Disconnect Size
Connector Wire Range
(Copper Wire Only)
ACZ
Unit
Size
AGZ
Unit
Size
Volts
Cir #1 Cir #2 Cir #1 Cir #2 Cir #1 Cir #2 Cir #1 Cir #2
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
380 175 175 14 GA – 2/0 14 GA – 2/0 250 250 #4 – 300 kcmil #4 – 300 kcmil
460 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
090B 075B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
380 175 175 14 GA – 2/0 14 GA – 2/0 250 250 #4 – 300 kcmil #4 – 300 kcmil
460 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
100B 085B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
380 175 175 14 GA – 2/0 14 GA – 2/0 250 250 #4 – 300 kcmil #4 – 300 kcmil
460 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
110B 090B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 400 #4 – 300 kcmil 250 – 500 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 400 #4 – 300 kcmil 250 - 500 kcmil
380 175 175 14 GA – 2/0 14 GA – 2/0 150 250 #14 - 1/0 #4 – 300 kcmil
460 175 175 14 GA – 2/0 14 GA – 2/0 150 250 #14 - 1/0 #4 – 300 kcmil
120B 100B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 400 400
250 – 500
250 – 500 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 400 400
250 – 500
kil
250 - 500kcmil
380 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 - 300kcmil
460 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 - 300kcmil
130B 110B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 400 400
250 – 500
250 - 500 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 400 400
250 – 500
kil
250 – 500 kcmil
380 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
460 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
140B 120B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
208 380 380 #4 – 500 kcmil #4 – 500 kcmil 400 400
250 – 500
250 – 500 kcmil
230 380 380 #4 – 500 kcmil #4 – 500 kcmil 400 400
250 – 500
kil
250 – 500 kcmil
380 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
460 380 380 #4 – 500 kcmil #4 – 500 kcmil 250 250 #4 – 300 kcmil #4 – 300 kcmil
155B 130B
575 175 175 14 GA – 2/0 14 GA – 2/0 150 150 #14 - 1/0 #14 - 1/0
All Electrical Data notes are on page 49.