Table 24, ACZ BC & AGZ BM Electrical Wiring, Single Point (Up to 105°F)
Power Supply
Field Wire
Recomm’d.
Fuse
Minimum
Max. Fuse
ACZ
AGZ
Unit
Size
Circuit
Or HACR
Unit
Volts
Or HACR
Wire
Ampacity
Breaker
Size
Breaker
Quantity
Gauge
(MCA)
Size
Size
75C
208 358 6 4/0 400 400
230 358 6 4/0 400 400
380 187 3 3/0 225 225
460 150 3 1/0 175 175
090B 075B
575 125 3 #1 150 150
208 380 6 250 450 450
230 380 6 250 450 450
380 219 3 250 250 250
460 171 3 2/0 200 200
100B 085B
575 136 3 1/0 150 150
208 414 6 300 500 500
230 414 6 300 500 500
380 248 3 250 300 300
460 188 3 3/0 225 225
110B 090B
575 146 3 1/0 175 175
208 463 6 350 500 500
230 463 6 300 500 500
380 260 3 300 300 300
460 199 3 3/0 225 225
120B 100B
575 171 3 2/0 175 175
208 528 6 -
(
2
)
300 600 600
230 528 6 - (2) 300 600 600
380 282 3 300 300 300
460 220 3 4/0 250 250
130B 110B
575 182 3 3/0 200 200
208 613 6 -
(
2
)
350 700 700
230 613 6 - (2) 350 700 700
380 323 3 400 350 350
460 248 3 250 250 250
140B 120B
575 198 3 3/0 225 225
208 613 6 -
(
2
)
350 700 700
230 613 6 - (2) 350 700 700
380 361 6 4/0 400 400
460 273 3 300 300 300
155B 130B
575 212 3 4/0 225 225
NOTES:
1. Units operating in ambient temperatures of 95°F (35°C) and above must use the Maximum Fuse or HACR
Breaker size.
49.
2. All Electrical Data notes are on page
3. (2) indicates that two conduits are required.
4. Conduit hubs are not supplied.
36 ACZ / AGZ-BM IMM ACZ/AGZ-4