Electrical Data Standard Ambient
Table 21, ACZ BC & AGZ BM Electrical Data, Single Point (105°F & below)
Power Su
pp
l
y
Field Wire
ACZ
Unit
Size
AGZ
Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Max. Fuse
Or HACR
Breaker
Size
208 133 3 1/0 150 150
230 126 3 #1 150 150
380 80 3 #4 90 90
460 68 3 #4 80 80
030B 026B
575 52 3 #6 60 60
208 146 3 1/0 175 175
230 143 3 1/0 175 175
380 88 3 #3 100 100
460 74 3 #4 80 90
035B 030B
575 58 3 #6 70 70
208 158 3 2/0 175 175
230 150 3 1/0 175 175
380 96 3 #3 110 110
460 79 3 #4 90 90
040B 035B
575 64 3 #6 70 70
208 167 3 2/0 200 200
230 167 3 2/0 200 200
380 113 3 #2 125 125
460 81 3 #4 90 90
045B 040B
575 70 3 #4 80 80
208 184 3 3/0 225 225
230 184 3 3/0 225 225
380 121 3 #1 125 125
460 94 3 #3 110 110
050B 045B
575 78 3 #4 90 90
208 199 3 3/0 225 225
230 199 3 3/0 225 225
380 127 3 #1 150 150
460 104 3 #2 125 125
055B 050B
575 86 3 #3 100 100
208 221 3 4/0 250 250
230 214 3 4/0 250 250
380 145 3 1/0 175 175
460 108 3 #2 125 125
060B 055B
575 96 3 #3 110 110
208 248 3 250 300 300
230 228 3 4/0 250 250
380 156 3 2/0 175 175
460 112 3 #2 125 125
065B 060B
575 105 3 #2 125 125
208 281 3 300 350 350
230 281 3 300 350 350
380 162 3 2/0 200 200
460 124 3 #1 150 150
070B 065B
575 109 3 #2 125 125
208 301 3 350 350 350
230 301 3 350 350 350
380 168 3 2/0 200 200
460 130 3 #1 150 150
080B 070B
575 112 3 #2 125 125
NOTES:
1. Units operating in ambient temperatures of 95°F (35°C) and above must use the Maximum Fuse or HACR
Breaker size.
2. All Electrical Data notes are on page
49.
3. Conduit hubs are not provided.