Unit installation
IOMM ACZ/AGZ-3  ACZ / AGZ-BM  5 
Location 
Unit Placement 
ACZ/AGZ units are for outdoor applications and can 
be mounted either on a roof or at ground level. For 
roof mounted applications, install the unit on a steel 
channel or I-beam frame to support the unit above the 
roof. For ground level applications, install the unit on 
a substantial base that will not settle. A one-piece 
concrete slab with footings extended below the frost 
line is recommended. Be sure the foundation is level 
within 1/2"(13mm) over its length and width. The 
foundation must be strong enough to support the 
weights listed in the Physical Data Tables beginning 
on page 26. 
Table 1, Recommended Minimum Clearances 
ACZ-BC 
Model Sizes 
AGZ-BM 
Model Size 
Coil Side “A” 
ft (m) 
“B” 
ft (m) 
“C” 
ft (m) 
End Opposite 
Controls ft (m) 
Control Panel End 
ft. (m) 
030B – 080B  026B – 070B  4 (1.2)  8 (2.4)  6 (1.8)  4 (1.2)  4 (1.2) 
090B – 155B  075B – 130B  6 (1.8)  12 (3.6)  8 (2.4)  4 (1.2)  4 (1.2) 
Clearances 
Do not block the flow of air to and 
from the condenser coil. Restricting 
airflow or allowing air recirculation 
will result in a decrease in unit 
performance and efficiency because 
discharge pressures are increased.  
There must be no obstruction above 
the unit that would deflect discharge 
air downward where it could be 
recirculated back to the inlet of the 
condenser coil. The condenser fans 
are propeller type and will not operate 
with ductwork. 
Install the unit with enough side 
clearance for air entrance to the coil 
and for servicing. Provide service 
access to the evaporator, compressors, 
electrical control panel and piping 
components. 
Do not allow debris to accumulate 
near the unit where it could be drawn 
into the condenser coil. Keep 
condenser coils and fan discharge free 
of snow or other obstructions to 
permit adequate airflow for proper 
operation. 
Figure 3, Clearances 
4 FT. (1220) 
CLEARANCE FOR
SERVICE ACCESS
4 FT. (1220mm)
CLEARANCE FOR
SERVICE ACCESS
SEE TABLE BELOW
DIMENSION “A”
SEE TABLE BELOW
DIMENSION “A”
The recommended minimum side clearance between two units
is dimension “B’ in table on this page. 
The unit must not be installed in a pit or enclosure that is
deeper or taller than the height of the unit unless extra space
is provided. The minimum clearance on each 
side of the unit is dimension “C” in table on this page.
AIR
DISCHARGE
AIR
DISCHARGE
AIR
DISCHARGE
AIR FLOW
A
IR FLOW
AIR FLOW
“B”
AIR FLOW
A
IR FLOW
“C” “C”