Unit installation
IOMM ACZ/AGZ-3  ACZ / AGZ-BM  41 
Electrical Data High Ambient 
Table 30, ACZ BC & AGZ BM Electrical Data, Single Point 
Power Supply 
Field Wire 
ACZ Unit 
Size 
AGZ 
Unit 
Size 
Volts 
Minimum 
Circuit 
Ampacity 
(MCA) 
Quantity 
Wire 
Gauge 
75C 
Recomm’d. 
Fuse 
Or HACR 
Breaker 
Size 
Max. Fuse 
Or HACR 
Breaker 
Size 
208
147
3
1/0
175
175
230  133  3  1/0  150  150 
380  80  3 #4 90  90 
460  68  3 #4 80  80 
030B 026B 
575  53  3 #6 60  60 
208
158
3
2/0
175
175
230  144  3  1/0  175  175 
380  88  3  #3  100  100 
460  74  3 #4 90  90 
035B 030B 
575  59  3 #6 70  70 
208
168
3
2/0
200
200
230  155  3  2/0  175  175 
380  96  3  #3  110  110 
460  80  3 #4 90  90 
040B 035B 
575  64  3 #6 70  70 
208
187
3
3/0
200
200
230  167  3  2/0  200  200 
380  113  3  #2  125  125 
460  84  3 #4 90  90 
045B 040B 
575  70  3 #4 80  80 
208
207
3
4/0
225
225
230  188  3  3/0  225  225 
380  123  3  #1  125  125 
460  94  3  #3  110  110 
050B 045B 
575  78  3 #4 90  90 
208
226
3
4/0
225
225
230  207  3  3/0  225  225 
380  132  3  1/0  150  150 
460  104  3  #2  125  125 
055B 050B 
575  86  3  #3  100  100 
208
249
3
250
250
250
230  229  3  4/0  250  250 
380  147  3  1/0  175  175 
460  115  3  #2  125  125 
060B 055B 
575  96  3  #3  110  110 
208
270
3
300
300
300
230  248  3  250  250  250 
380  160  3  2/0  175  175 
460  124  3  #1  150  150 
065B 060B 
575  105  3  #2  125  125 
208
303
3
350
350
350
230  282  3  300  350  350 
380  164  3  2/0  200  200 
460  138  3  1/0  175  175 
070B 065B 
575  115  3  #2  125  125 
208
323
3
400
400
400
230  304  3  350  350  350 
380  172  3  2/0  200  200 
460  150  3  1/0  175  175 
080B 070B 
575  123  3  #1  150  150 
NOTES: 
1.  Units operating in ambient temperatures above 95°F (35°C) must use the Maximum Fuse or HACR Breaker size 
2.  All Electrical Data notes are on page 47. 
3.  Conduit hubs are not provided. 