Unit installation
18 ACZ / AGZ-BM IOMM ACZ/AGZ-3
CAUTION
Do not use an automotive grade antifreeze. Industrial grade glycols must be used.
Automotive antifreeze contains inhibitors which will cause plating on the copper tubes
within the chiller evaporator. The type and handling of glycol used must be consistent
with local codes.
Table 8, Ethylene Glycol Factors for Models AGZ 026BM to 070BM
Freeze Point
% E.G.
o
F
o
C
Capacity Power Flow PD
10 26 -3.3 0.998 0.998 1.036 1.097
20 18 -7.8 0.993 0.997 1.060 1.226
30 7 -13.9 0.987 0.995 1.092 1.369
40 -7 -21.7 0.980 0.992 1.132 1.557
50
-28 -33.3 0.973 0.991 1.182 1.791
Table 9, Propylene Glycol Factors for Models AGZ 026BM to 070BM
Freeze Point
% P.G.
o
F
o
C
Capacity Power Flow PD
10 26 -3.3 0.995 0.997 1.016 1.100
20 19 -7.2 0.987 0.995 1.032 1.211
30 9 -12.8 0.978 0.992 1.057 1.380
40 -5 -20.6 0.964 0.987 1.092 1.703
50
-27 -32.8 0.952 0.983 1.140 2.251
Table 10, Ethylene Glycol Factors for Models AGZ 075BM to 130BM
Freeze Point
% E.G.
o
F
o
C
Capacity Power Flow PD
10 26 -3.3 0.994 0.998 1.038 1.101
20 18 -7.8 0.982 0.995 1.063 1.224
30 7 -13.9 0.970 0.992 1.095 1.358
40 -7 -21.7 0.955 0.987 1.134 1.536
50
-28 -33.3 0.939 0.983 1.184 1.755
Table 11, Propylene Glycol Factors for Models AGZ 075BM to 130BM
Freeze Point
% P.G.
o
F
o
C
Capacity Power Flow PD
10 26 -3.3 0.988 0.996 1.019 1.097
20 19 -7.2 0.972 0.992 1.035 1.201
30 9 -12.8 0.951 0.987 1.059 1.351
40 -5 -20.6 0.926 0.979 1.095 1.598
50
-27 -32.8 0.906 0.974 1.142 2.039
Altitude Correction Factors
Performance tables are based at sea level. Elevations other than sea level affect the performance of
the unit. The decreased air density will reduce condenser capacity, consequently reducing the unit's
performance. For performance at elevations other than sea level refer to Table 12 or Table 13.