Unit installation
14  ACZ / AGZ-BM  IOMM ACZ/AGZ-3 
Table 5, Isolator Locations 
ACZ-BS, AGZ-BM Less Evaporator Units 
Operating 
Weight 
Neoprene-In-Shear Mountings  Spring-Flex Mountings 
ACZ-
BS 
Model 
AGZ-
BM 
Model 
lbs kg 1 2 3 4 5  6  1  2  3 4 (1) 5  6 
030 026 
3600 1631 Black Gray Gray Green -  -  Orange Purple Red Orange    
035 030 
3600 1631 Black Gray Gray Green -  -  Orange Purple Red Orange -  - 
040 035 
3600 1631 Black Gray Gray Green -  -  Orange Purple Red Orange -  - 
045 040 
3610 1635 Black Gray Gray Green -  -  Orange Purple Purple Orange -  - 
050 045 
3650 1653 Black Gray Gray Green -  -  Orange Purple Purple Orange -  - 
055 050 
3800 1721 Black Gray Gray Green -  -  Orange Purple Purple Orange -  - 
060 055 
3850 1744 Black Gray Gray Green -  -  Orange Purple Purple Orange -  - 
065 060 
4040 1830 Black Gray Gray Green -  -  Orange Purple Purple Orange -  - 
070 065 
4070 1844 Black Black Gray Gray  -  -  Orange Purple Purple Red  -  - 
080 070 
4180 1894 Black Black Gray Gray  -  -  Orange Orange Purple Red  -  - 
090 075 
5630 2550 Red Black Red Black -  -  Green Orange Green Orange -  - 
100 085 
5790 2623 Red Black Red Black -  -  Green Orange Green Orange -  - 
110 090 
5950 2695 Red Black Red Black -  -  Green Orange Green Orange -  - 
120 100 
6970 3157 Black Black Black Black Black Black Orange Orange Purple Orange Orange Purple
130 110 
7230 3275 Black Black Black Black Black Black Orange Orange Purple Orange Orange Purple
140 120 
7480 3388  Red Black Black Red Black Black Green Orange Purple Green Orange Purple
155 130 
7760 3515  Red Black Black Red Black Black Green Orange Purple Green Orange Purple
NOTE (1): Position #4 is a CP-1, single spring isolator for ACZ 030 to 065 and AGZ 026 to 060. All others are CP-2, 
two
 spring. 
Ambient Temperature and Water Flow Limitations 
ACZ/AGZ units are designed to operate in ambient temperatures as shown in the following table. 
Table 6, Unit Maximum Operating Ambient Temperature 
Unit Model  Standard Controls 
w/ Low Ambient VFD 
Control Option 
w/ Low Ambient VFD Control 
Plus High Ambient Panel Option 
AGZ 026B – 130B 
ACZ 030B – 155B 
115°F 105°F 125°F 
The VFD Low Ambient Control Option imposes an additional heat load on the control panel 
limiting operation to 105°F ambient temperature. The addition of the High Ambient Panel 
Option allows operation to 125°F ambient temperature. 
Compressor loading and unloading is adaptively determined by system load, ambient air 
temperature, and other inputs to the MicroTech control algorithms. An optional low ambient fan 
VFD option allows operation down to 0°F (-18°C). The minimum ambient temperature is based 
on still conditions where the wind is not greater than five mph. Greater wind velocities will 
result in reduced discharge pressure, increasing the minimum operating ambient temperature.  
Field-installed hail/wind guards are available to allow the chiller to operate effectively down to 
the ambient temperature for which it was designed. 
Evaporator flow rates can be found on page 23. Operation below the minimum values can result 
in laminar flow causing freeze-up problems, scaling and poor control. Flow rates above the 
maximum values will result in unacceptable pressure drops and can cause excessive erosion, 
potentially leading to failure. 
Water Piping (Model AGZ-BM) 
Local authorities can supply the installer with the proper building and safety codes required for 
safe and proper installation. 
Install piping with minimum bends and changes in elevation to minimize pressure drop. The 
following issues must be considered when designing and installing water piping: 