Unit installation
132  ACZ / AGZ-BM  IOMM ACZ/AGZ-3 
5.  Check the unit subcooling value by reading the liquid line pressure and temperature at the liquid 
line near the filter-drier. The subcooling values should be between 15 and 20 degrees F (8.3 and 
11.1 degrees C). 
6.  With outdoor temperatures above 60°F (15.6°C) all condenser fans should be operating and the 
liquid line temperature should be within 5°F-10°F (2.8°C-5.6°C) of the outdoor air temperature. 
At 25-50% load the liquid line temperature should be within 5°F (2.8°C) of outdoor air 
temperature with all fans on. At 75-100% load the liquid line temperature should be within 10°F 
(5.6°C) of outdoor air temperature with all fans on. 
7.  Overcharging of refrigerant will raise the compressor discharge pressure due to filling of the 
condenser tubes with excess refrigerant. 