Unit installation
IOMM ACZ/AGZ-3  ACZ / AGZ-BM  127 
The power element is removable from the valve body without removing the valve from the line. 
NOTE: Before adjusting superheat, check that unit charge is correct and liquid line sight 
glass is full with no bubbles and that the circuit is operating under stable, full load 
conditions. 
The suction superheat for the suction leaving the evaporator is set at the factory for 8 to 12 degrees F 
at full load. To have full rated unit performance, the superheat must be about 8 degrees F at 95°F 
outdoor ambient temperature. 
Crankcase Heaters 
The scroll compressors are equipped with externally mounted band heaters located at the oil sump 
level. The function of the heater is to keep the temperature in the crankcase high enough to prevent 
refrigerant from migrating to the crankcase and condensing in the oil during off-cycle. 
NOTE: Power must be supplied to the heaters 24 hours before starting the compressors. 
Evaporator 
Models AGZ 026 through 070 
The evaporator is a compact, high efficiency, dual circuit, brazed plate-to-plate type heat exchanger 
consisting of parallel stainless steel plates. 
The evaporator is protected with an electric resistance heater and insulated with 3/4" (19mm) thick 
closed-cell polyurethane insulation.  This provides freeze protection down to -20°F (-29°C) ambient 
air temperature. 
The water side working pressure is 363 psig (2503 kPa). Evaporators are designed and constructed 
according to, and listed by, Underwriters Laboratories (UL). 
Models AGZ 075 through 130 
The evaporator is direct expansion, shell-and-tube type with water flowing in the baffled shell side 
and refrigerant flowing through the tubes. Two independent refrigerant circuits within the 
evaporator serve the unit's dual refrigerant circuits. 
The evaporator has a carbon steel shell and seamless high efficiency copper tubes, roller expanded 
into a carbon steel tube sheet. 
3/8" (10mm) vent and drain plugs are provided on the top and bottom of the shell. 
The evaporator is wrapped with an electric resistance heater cable and insulated with 3/4" (19mm) 
thick vinyl nitrate polymer sheet insulation, protecting against water freeze-up at ambient air 
temperatures to -20°F (-29°C). An ambient air thermostat controls the heater cable. The fitted and 
glued-in-place insulation has a K factor of 0.28 Btu in/hr ft
2
 at 75°F. 
The refrigerant (tube) side maximum working pressure is 300 psig (2068 kPa). The water-side 
working pressure is 152 psig (1048 kPa). Each evaporator is designed, constructed, inspected, and 
stamped according to the requirements of the ASME Boiler and Pressure Vessel Code. Double 
thickness insulation is available as an option. 