Unit installation
118  ACZ / AGZ-BM  IOMM ACZ/AGZ-3 
Active Alarm 
Alarm Active
Alarm Description
Time/Date
. 
Alarm Active
No more alarms
Press ENTER to clear
all active alarms
If the unit is off on a shutdown alarm, or running but in a limit alarm condition, the cause, date/time, 
and UNIT STATUS will appear in the ALARM ACTIVE screen. The remote alarm relay will close, 
and a red light will appear behind the LEFT button. The light will go out when the fault is cleared.  
If there is a simultaneous occurrence of more than one alarm, the others will appear in additional 
screens below this one, accessed by the DOWN ARROW. 
If an alarm occurs, press the MENU button, then the LEFT button for ALARM, and then the left 
button again to reach the ALARM ACTIVE screen. 
The cause of the alarm must be remedied before attempting to clear the alarm. To clear the alarm(s), 
scroll down to the last screen (bottom screen above) and press ENTER. The SET UNIT SPs screen 
will appear and the password will be asked for. Press ENTER and the cursor will flash in the 
password field. Press the UP button to scroll the numbers up to the required password. Then press 
ENTER to enter the password. Then return to the ALARM ACTIVE screen and press ENTER to 
clear the alarm. 
If other faults have appeared, they will all be cleared at the same time. 
SET MENUS 
Changing setpoints; setpoints are changed as follows: 
1.  A password must be entered before attempting to change any setpoint. Two four-digit passwords 
provide OPERATOR and MANAGER levels of access to setpoints. The passwords are 
preprogrammed into the controller. The Operator Password is 0100, the Manager Password is 
2001. Either password must be entered using the ENTER PASSWORD screen (15) before a 
protected setting can be changed. The quickest way to reach screen (15) is to press the MENU 
key, then press SET (UP Arrow Key), then press the UP Arrow key, which will go to screen (15). 
Press ENTER to reach the numerical field, hold the UP Arrow key to scroll the numbers up to 
the desired password, then press ENTER. The word “Operator” or “Manager” will appear next 
to Level when the password is entered properly. Setpoints can now be changed. Once entered, a 
password remains valid for 15 minutes after the last key-press. 
2.  Select the desired menu by scrolling through SET menus with the UP, DOWN, LEFT and 
RIGHT ARROWS. Alternatively, press the MENU button, select the type of setpoint desired, 
then scroll up or down to the desired menu screen. 
3.  When the desired menu screen is reached, select the desired field within the menu by moving 
between lines using the ENTER key. Some fields may not be accessible due to settings in other 
menus. 
4.  If a numerical value is being changed, use the INCREMENT key (UP ARROW) to increase or 
the DECREMENT key (DOWN ARROW) to decrease the value of the setpoint. 
5.  If a word type setpoint (for example, YES or NO) is to be selected, the choices are pre-loaded 
into the menu and selected by scrolling through the available setpoint options using the UP 
ARROW key. 