Unit installation

106 ACZ / AGZ-BM IOMM ACZ/AGZ-3
Symptom
Condition
Probable Cause Solution
Was power turned OFF after a
parameter edit but before pressing the
Store key?
Edit the data and press the Store key once.
No
downloads
have
occurred.
Edits to data are permanently stores at
power down. Was the time from power
OFF to power ON less than six seconds?
Wait six seconds or more before turning
power OFF after editing data.
Inverter data
is not correct.
A download
to the
inverter was
attempted.
Was the power turned OFF within six
seconds after the display changed from
REMT to INV?
Copy data to the inverter again, and keep
power ON for six seconds or more after
copying.
True for
certain
parameters.
Is the inverter in Run Mode? Some
parameters cannot be edited during Run
Mode.
Put inverter in Stop Mode (press the
Stop/reset key). Then edit the parameter.
A parameter
will not
change after
an edit
(reverts to old
setting).
True for all
parameters.
If you’re using the [SFT] intelligent input
(software lock function)is the [SFT]
input ON?
Change the state of the SFT input, and
check the B_31 parameter (SFT mode).
Monitoring Trip Events, History. & Conditions
Fault Detection and Clearing
The microprocessor in the inverter detects a variety of fault
conditions and captures the event, recording it in a history table. The
inverter output turns OFF, or “trips” similar to the way a circuit
breaker trips due to an over-current condition. Most faults occur
when the motor is running (refer to the diagram to the right).
However, the inverter could have an internal fault and trip in Stop
Mode. In either case, you can clear the fault by pressing the
Stop/Reset key.