Unit installation

IOMM ACZ/AGZ-3 ACZ / AGZ-BM 101
Normal Operation - Staging Up
At startup, the first fan will start when the saturated condenser temperature rises above the target.
After this, the stage up deadbands apply.
When the saturated condenser temperature is above the Target + the active deadband, a Stage Up
error is accumulated.
Stage Up Error Step = Saturated Condenser Refrigerant temperature – (Target + Stage Up
deadband)
The Stage Up Error Step is added to Stage Up Accumulator once every Stage Up Error Delay
seconds. When the Stage Up Error Accumulator is greater than the Stage Up Error Setpoint, another
stage is started.
When a stage up occurs, or the saturated condenser temperature falls back within the Stage Up
deadband, the Stage Up Accumulator is reset to zero.
Normal Operation - Staging Down
There are four Stage Down deadbands, one for each stage.
When the saturated condenser refrigerant temperature is below the Target – the active deadband, a
Stage Down error is accumulated.
Stage Down Error Step = (Target Stage Down deadband) Saturated Condenser Refrigerant
temperature
The Stage Down Error Step is added to Stage Down Accumulator once every Stage Down Error
Delay seconds. When the Stage Down Error Accumulator is greater than the Stage Down Error
Setpoint, another stage of condenser fans turns off. The last stage on will not shut off until the
circuit is in an off state.
When a stage down occurs, or the saturated temperature rises back within the Stage Down deadband,
the Stage Down Error Accumulator is reset to zero.
Forced Fan Stage At Start
Fans may be started simultaneously with the compressor based on outdoor ambient temperature.
When the compressor starts, a Fantrol stage is forced based on the following table.
Table 59, Forced Fan at Start
OAT Fantrol Stage At Start
> 75
o
F Forced Fan 1 SP
> 90
o
F Forced Fan 2 SP
> 105
o
F Forced Fan 3 SP
Up to four fans may be forced on when the compressor starts. If the unit has the VFD option, then
only three fans can start with the compressor, and the VFD will start normally when the saturated
condenser temperature is higher than the target.
After forcing fans on, the saturated condenser temperature may temporarily stay below the target by
some amount. In order to keep these fans from staging off, no stage down error can be accumulated
until either the OAT drops below 75
o
F, or the saturated condenser temperature goes above the target.