Unit installation
IOMM ACZ1-2 ACZ 010A through 039A 45
SET UNIT SPs (7)
Evaporator Refrig
Press Sensor
Offset= 00.0 psi
The pressure offsets on menus 7 and 8 and the temperature offset on menu 9 correct the
controller's display of the parameters. The sensors used in these units have a high degree of
repeatability but may need correction (offset). An accurate pressure gauge or thermometer
is used to determine the correct temperature or pressure. A positive or negative offset value
is then entered to make the controller reading agree with the measured value.
SET UNIT SPs (8)
Condenser Refrig
Press Sensor
Offset= 00.0 psi
SET UNIT SPs (9)
Outside Ambient
Temperature Sensor
Offset= 00.0
o
F
SET UNIT SPs (10)
ENTER PASSWORD XXXX
Active Password
Level:None
Two four-digit passwords provide OPERATOR and MANAGER levels of access to
changeable parameters. The passwords are preprogrammed into the controller. The
Operator Password is 0100. Either password must be entered using the ENTER
PASSWORD (12) screen before a protected setting can be changed.
This screen can be accessed either through the SET OTHER menu or by simply pressing
the ENTER key while on one of the SET screens. The controller will automatically go
from the screen with the setting change to this screen. After the correct password has been
entered, the controller will automatically return to the original set screen.
Once a password has been entered, it remains valid for 15 minutes after the last key-press.
SET COMP SPs
SET COMP SPs (1)
Clear Cycle Tmr=No
Stop-Start =XXmin
Start-Start =XXmin
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a
compressor after it has stopped. Start-Start is the time required before starting a
compressor after the last time it has started. It is recommended that these default values
not be changed.
SET COMP SPs (2)
InterStageUp=XXXsec
InterStageDn=XXXsec