Unit installation

36 ACZ 010A through 039A IOMM ACZ1-2
Compressor State
A compressor will start when all of the following are true:
The compressor is “next on”
Stage Up Now is set
The compressor is available to start
A compressor will stop when any of the following conditions are true:
Unit state = Off
Evap flow alarm active
Low Ambient start attempt failed
Stage Down Now is set, both compressors are running, and the compressor is “next
off”
Pumpdown is complete
Normal Shutdown
If a condition arises that requires the unit to shut down, a pumpdown will be performed if it
is not an emergency situation. A normal shutdown will be initiated when any of the
following occur:
Unit State = Pumpdown
Low Ambient Lockout
A normal stagedown occurs, and only one compressor is running
Pumpdown Procedure
If both compressors are running, shut off the appropriate compressor based on
sequencing logic
With one compressor left running, turn off hot gas output and liquid line output
Keep running until evaporator pressure reaches the pumpdown pressure, then stop
compressor
If evaporator pressure does not reach pumpdown pressure within two minutes, stop
compressor and log pumpdown failure alarm
Rapid Shutdown
A situation may arise that requires the unit to shut down immediately, without doing a
pumpdown. This rapid shutdown will be triggered by any of the following:
Unit State = Off
Stop Alarm
Low ambient start attempt failed
All compressor and liquid line outputs will be turned off immediately for a rapid shutdown.
Liquid Line Solenoid
The liquid line output will be on any time a compressor is running and the unit is not
performing a pumpdown. This output will be off at all other times.