Association Groups:
Group Number Maximum Nodes Description
1 1 Lifeline
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further
enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the
desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the
same logic applies: Values greater than 32768 may needed to be given as negative values too.
Parameter 1: Upload temperature format automatically
Size: 1 Byte, Default Value: 2
Setting Description
0 Celsius
1 Fahrenheit
2 Follow the main display
Parameter 2: Upload temperature automatically
Size: 1 Byte, Default Value: 3
Setting Description
0 Off
1 Upload the difference value only
2 Timing upload mode only
3 Upload the difference+timing upload mode
Parameter 3: Upload temperature difference
Size: 2 Byte, Default Value: 5
Setting Description
3 - 1000 Base on 0.1 unit
Parameter 4: Upload time interval regularly
Size: 2 Byte, Default Value: 30
Setting Description
10 - 65535 Base on 1s unit, it suggest to be set above 30s
Parameter 255: Factory setting
Parameters setting back to default value, association groups deleted