TROUBLE SHOOTING 
Basic Air Conditioning Trouble Shooting Check List 
1.  Check manufacturer’s nameplate located on the unit for correct power supply.
2.  Turn the power to the unit on. The evaporator (Enclosure or “COLD” air) blower should come on. 
Is there airflow? 
  YES, proceed to step # 3. 
 NO, possible:  Open motor winding  
 Stuck blower motor  
 Obstructed wheels/blades   
3.  Check thermostat setting? Adjust thermostat to the lowest setting
. This should turn the 
condenser blower and the compressor on. Did condenser blower and compressor come on when the 
thermostat was turned on? 
  YES, proceed to step #4. 
 NO, possible:  Defective thermostat  
4.  Are both blowers and the compressor running? If not the unit will not cool properly. 
5.  Check condenser ( Ambient or “HOT” air ) blower for airflow. Is there airflow ? 
  YES, proceed to step # 6. 
 NO, possible:  Defective thermostat  
 Open motor winding  
 Stuck blower motor  
 Obstructed wheels/blades   
6.  Carefully check the compressor for operation - motor should cause slight vibration, and the outer 
case of the compressor should be warm. 
  YES, wait 5 minutes, then proceed to step #7. 
  NO, possible:    Defective thermostat 
 Defective capacitor    
 Defective overload    
 Defective relay   
7  Make sure the coils are clean. Then check evaporator “air in” and “air out” temperatures. If the 
temperatures are the same: 
        Possible loss of refrigerant     
        Possible bad valves in the compressor  
8.  To check for a bad thermostat. Turn power to the unit off. Remove control box cover, place both 
thermostat wires onto one terminal (replace control box cover for safety). This will bypass the 
switch in the thermostat. Turn the power on. If both blowers and the compressor come on, the 
thermostat needs to be replaced. 
Repair or Replace 
defective parts. 
Re
p
lace 
p
art.
Repair or Replace 
defective parts. 
Repair or Replace 
defective parts. 
Repair or Replace 
defective parts. 
317-257-6811 www.McLeanParts.net 317-257-1590 fax