Instruction manual

© 2015 Pentair Equipment Protection
89104462
- 11 -
M28 DESIGN DATA
Model Availability Voltage Hz
Full Load
Amps
Phase
BTU/Hr. @
Max Ambient
Temperature
Max Ambient
Temperature
(°F/°C)
Shipping
Weight
(lb./kg)
M28-0216-G013 STOCK 100/115 50/60 8.3/8.4 1 2200/2200 125/52 97/44
M28-0216-GXXX 100/115 50/60 8.3/8.4 1 2200/2200 125/52 97/44
M28-0226-G004 STOCK 220/230 50/60 4.2/4.2 1 2200/2200 125/52 97/44
M28-0226-GXXX 220/230 50/60 4.2/4.2 1 2200/2200 125/52 97/44
M28-0416-G007 STOCK 115 50/60 14.6/14.0 1 3800/4000 125/52 116/53
M28-0416-GXXX 115 50/60 14.6/14.0 1 3800/4000 125/52 116/53
M28-0426-G032 STOCK 230 50/60 7.4/6.9 1 3800/4000 125/52 116/53
M28-0426-GXXX 230 50/60 7.4/6.9 1 3800/4000 125/52 116/53
M28-0616-GXXX 115 50/60 16.4/17.2 1 5400/6000 125/52 120/55
M28-0626-GXXX 230 50/60 8.0 1 5400/6000 125/52 120/55
-XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers.
M28 DIMENSIONAL DRAWING