GENESIS™ Air Conditioners All Models INSTRUCTION MANUAL Rev.
TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER................................................................................................................................................................................3 HANDLING AND TESTING THE AIR CONDITIONER.......................................................................................................................................................3 INSTALLATION INSTRUCTIONS.....................................................................
RECEIVING THE AIR CONDITIONER Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents, scratches, loose assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier.
INSTALLATION INSTRUCTIONS 1. Inspect air conditioner. Verify functionality before mounting the air conditioner, seeHANDLING AND TESTING THE AIR CONDITIONER on page 3. 2. Using the cutout dimensions shown in this manual or the cutout template printed on the units shipping carton, prepare the air “IN” and air “OUT” openings, and mounting bolt hole pattern for the enclosure. 3. Using the gasket kit provided, install gaskets to air conditioner. See gasket kit illustration in this manual for proper location. 4.
M13 DESIGN DATA Model M13-0116-G1014 Availability Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) Stock 100/115 50/60 3.7/3.9 1 800/1000 125/52 46/21 100/115 50/60 3.7/3.9 1 800/1000 125/52 46/21 220/230 50/60 2.6/2.6 1 800/1000 125/52 46/21 220/230 50/60 2.6/2.
Mounting gasket kit 17-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. Dashed lines represent aire conditioner. M13 COMPONENTS LIST Part Number Item Number.
M13 SCHEMATIC AND WIRE DIAGRAM, 115/230 VOLT 1000 BTU 89104462 © 2015 Pentair Equipment Protection -7-
M17 DESIGN DATA Model M17-0216-G009 Availability Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) Stock 100/115 50/60 7.2/6.9 1 1500/1800 125/52 56/25 100/115 50/60 7.2/6.9 1 1500/1800 125/52 56/25 220/230 50/60 3.1/3.1 1 1500/1800 125/52 56/25 220/230 50/60 3.1/3.
Mounting gasket kit 17-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. Dashed lines represent aire conditioner. M17 COMPONENTS LIST Part Number Item Number.
M17 SCHEMATIC AND WIRE DIAGRAM, 115/230 VOLT 1800 BTU - 10 - © 2015 Pentair Equipment Protection 89104462
M28 DESIGN DATA Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) 100/115 50/60 8.3/8.4 1 2200/2200 125/52 97/44 100/115 50/60 8.3/8.4 1 2200/2200 125/52 97/44 220/230 50/60 4.2/4.2 1 2200/2200 125/52 97/44 220/230 50/60 4.2/4.2 1 2200/2200 125/52 97/44 115 50/60 14.6/14.0 1 3800/4000 125/52 116/53 115 50/60 14.6/14.0 1 3800/4000 125/52 116/53 230 50/60 7.4/6.
M28 MOUNTING GASKET AND CUTOUT DIMENSIONS (3.) Mounting gasket kit 28-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. - 12 - 1. Dashed lines represent air conditioner. 2. Cutout dimensions are for standard unit. 3. Hole may be deleted if service cord is routed through 3.00 x 13.50 cutout (except on units with electric heat).
M28 COMPONENTS LIST Part Number (115 Volt) Item Number.
M28 SCHEMATIC AND WIRE DIAGRAM, 115/230 VOLT, 2200 BTU - 14 - © 2015 Pentair Equipment Protection 89104462
M28 SCHEMATIC AND WIRE DIAGRAM, 115/230 VOLT, 4000 BTU & 230 VOLT 6000 BTU M28 SCHEMATIC AND WIRE DIAGRAM, 115 VOLT, 6000 BTU 89104462 © 2015 Pentair Equipment Protection - 15 -
M33 DESIGN DATA Model M33-0416-G010 Availability Stock M33-0416-GXXX M33-0426-G009 M33-0426-GXXX Stock Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) 115 50/60 11.6/10.8 1 3700/4000 131/55 105/48 115 50/60 11.6/10.8 1 3700/4000 131/55 105/48 230 50/60 7.2/7.3 1 3700/4000 131/55 105/48 230 50/60 7.2/7.
M33 MOUNTING GASKET AND CUTOUT DIMENSIONS Mounting gasket kit 33-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. 89104462 1. Dashed lines represent aire conditioner. 2. Cutout dimensions for standard unit. 3. Service cord to be routed through 2.00 x 11.12 cutout. 4. Bottom cutout will accomodate air conditioner or heat exchanger.
M33 COMPONENTS LIST Part Number (4000 BTU) Item Number 115 Volt 230 Volt Blower, Condenser, Top Discharge 1 38-2019-04 38-2020-04 Blower, Condenser, Front Discharge 1 38-2019-00 38-2020-00 Fan, Evaporator 2 12-1012-01 12-1012-02 Capacitor, Compressor, Run 3 N/A 89100497 Capacitor, Compressor, Start 4 N/A 89100496 Coil, Condenser 5 33-2001-01 33-2001-01 Coil, Evaporator 6 33-2002-02 33-2002-02 Control Panel Assembly, Narrow N/S 10-1106-100 10-1106-100 Filter, Air, Reusable
M33 WIRE DIAGRAM AND SCHEMATIC, 115 V, 4000 BTU 89100994 WIRE DIAGRAM, 230 V, 4000 BTU 89104462 © 2015 Pentair Equipment Protection - 19 -
M36 DESIGN DATA Model M36-0616-G307 Availability Stock M36-0616-GXXX M36-0626-G306 M36-0626-GXXX Stock Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) 115 50/60 10.0/10.0 1 5000/6000 105/48 115 50/60 10.0/10.0 1 5000/6000 105/48 230 50/60 5.0/5.0 1 5000/6000 105/48 230 50/60 5.0/5.0 1 5000/6000 105/48 -XXX will be replaced with a three-digit number designating all desired options.
M36 MOUNTING GASKET AND CUTOUT DIMENSIONS Mounting gasket kit 36-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. 89104462 1. Dashed lines represent aire conditioner. 2. Cutout dimensions for standard unit. 3. Service cord to be routed through 3.00 x 14.00 cutout.
M36 COMPONENTS LIST Part Number (6000 BTU) Item Number 115 Volt 230 Volt Blower, Condenser 1 38-2019-04 38-2020-04 Blower, Evaporator 2 28-1064-06M 28-1064-05M Capacitor, Compressor, Run 3 52-6032-06 S-6173 Coil, Condenser 4 36-1017-01 36-1017-01 Coil, Evaporator 5 28-1001-01 28-1001-01 Part Description Compressor, Rotary 6 10-1016-91 10-1026-123 Control Panel Assembly, Wide N/S 10-1106-101 10-1106-101 Filter, Air, Reusable, Wide N/S 10-1000-56 10-1000-56 7 52-6028-00
M52 DESIGN DATA Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) M28-0626-GXXX 115 50/60 13.0/13.0 1 5000/6000 125/52 155/70 M52-0626-XXX 230 50/60 6.5/6.5 1 5000/6000 125/52 155/70 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73 110/115 50/60 18.9/19.
M52 MOUNTING GASKET AND CUTOUT DIMENSIONS Mounting gasket kit 52-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. - 24 - 1. Dashed lines represent air conditioner. 2. Cutout dimensions for standard unit. 3. Hole may be deleted if service cord is routed through 4.50 x 15.63 cutout (except on units with electric heat).
M52 COMPONENTS LIST Part Number (115 Volt) Item Number 6000 BTU 8000 BTU 10000 BTU 12000 BTU Blower, Condenser 1 52-6034-10 52-6034-10 52-6034-10 52-6034-10 Blower, Evaporator 2 52-6075-00 52-6075-00 52-6075-00 52-6034-10 Capacitor, Compressor, Run 3 52-6031-01 52-6032-01 52-6032-01 52-6032-01 Coil, Condenser 4 52-6111-00 52-6111-00 52-6111-00 52-6111-03 Coil, Evaporator 5 28-1001-01 52-6002-02 52-6121-01 52-6121-01 Part Description Compressor, AK 6 10-1016-08 10-1016
M52 SCHEMATIC AND WIRE DIAGRAM, 115 VOLT 10000 AND 12000 BTU M52 SCHEMATIC AND WIRE DIAGRAM, 115/230 VOLT 6000/8000 BTU AND 230 VOLT 10000/12000 BTU - 26 - © 2015 Pentair Equipment Protection 89104462
MHB11 DESIGN DATA Model MHB11-0216-G306 Availability STOCK MHB11-0216-G3XX MHB11-0226-G306 STOCK MHB11-0226-G3XX MHB11-0416-G307 STOCK MHB11-0416-G3XX MHB11-0426-G306 MHB11-0426-G3XX STOCK Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) 115 50/60 9.6/8.4 1 2200/2400 125/52 90/41 115 50/60 9.6/8.4 1 2200/2400 125/52 90/41 230 50/60 4.3/4.2 1 2100/2400 125/52 90/41 230 50/60 4.3/4.
MHB11 MOUNTING GASKET AND CUTOUT DIMENSIONS Mounting gasket kit 11-1000-50 included. Apply gasket to the bottom of the air conditioner before mounting to enclosure. - 28 - 1. Dashed lines represent air conditioner. 2. Cutout dimensions are for standard unit.
MHB11 COMPONENTS LIST Part Number (115 Volt) Part Number (230 Volt) Item Number 2200 BTU 4000 BTU 2200 BTU 4000 BTU Blower, Condenser 1 28-1064-06M 28-1064-06M 28-1064-05M 28-1064-05M Blower, Evaporator 2 28-1064-06M 28-1064-06M 28-1064-05M 28-1064-05M Capacitor, Compressor, Start 3 N/A 10-1032-13 N/A 10-1032-14 Coil, Condenser 4 11-3001-03 11-3001-03 11-3001-03 11-3001-03 Coil, Evaporator 5 11-1002-00 11-1002-00 11-1002-00 11-1002-00 Part Description Compressor, AE/AK/
MHB11 SCHEMATIC AND WIRE DIAGRAM, 115 AND 230 VOLT, 2200 BTU 04-2001-009 Rev D 05-2001-004 Rev A MHB11 SCHEMATIC AND WIRE DIAGRAM, 115/230 VOLT, 4000 BTU - 30 - © 2015 Pentair Equipment Protection 89104462
NOTES 89104462 © 2015 Pentair Equipment Protection - 31 -
TEMPERATURE CONTROL The electromechanical thermostat is factory preset to 75°F/23°C. To change the temperature setting, remove the front cover and screen. Use a standard screwdriver to adjust thermostat. For cooler temperatures turn clockwise, for warmer temperatures turn counterclockwise. PRINCIPLES OF OPERATION If electrical power to the air conditioner is interrupted and reapplied immediately, (within 3 to 5 seconds), the compressor may not restart due to the high back pressure of the compressor.
HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding capacity and a minimum amount of resistance to air flow. Because they are constructed entirely of aluminum they are lightweight and easy to service. Optimum filter performance is maintained by recoating the filters after washing with RP Super Filter Coat adhesive.
TROUBLE SHOOTING BASIC AIR CONDITIONING TROUBLE SHOOTING CHECK LIST 1. Check manufacturer’s nameplate located on the unit for correct power supply. 2. Turn on power to the unit. The evaporator (Enclosure or “COLD” air) blower should come on. Is there airflow? YES, proceed to step 3. NO, possible problem: • • • Open motor winding Stuck blower motor Obstructed blades Repair or Replace defective part 3. Check thermostat setting and adjust thermostat to the lowest setting.
SYMPTOMS AND POSSIBLE CAUSES: SYMPTOM POSSIBLE CAUSE Impellers/blowers not running Unit won’t cool Compressor not running Compressor runs, but has bad valves Loss of refrigerant Low line voltage at start. Should be +/-10% rated voltage.
NOTES - 36 - © 2015 Pentair Equipment Protection 89104462
NOTES 89104462 © 2015 Pentair Equipment Protection - 37 -
WARRANTY C. D. A. B. Pentair Equipment Protection warrants that the Goods manufactured by Pentair Equipment Protection will be free from defects in material and workmanship for a period of one (1) year from the date of shipment by Pentair Equipment Protection, subject to the following conditions and exclusions: Conditions. All Goods must be installed and operated according to the following specifications: 1. Maximum voltage variation no greater than plus or minus 10% of nameplate nominal rating; 2.
A. An RMA # will be issued by our Product Return Department in Anoka, MN at 763-422-2211. Buyer should have following information available at time of RMA request: 1. Complete Model Number, Serial Number and description of damaged unit being returned. 2. Original Buyer Purchase Order number and date product was received by Buyer. 3. Quantity to be returned and a brief description of failure for each unit, if different. 4.