M52 Design Data
Model Availability Voltage Hz
Full Load
Amps
Phase
BTU/Hr. @
Max Ambient
Temperature
Max Ambient
Temperature
(°F/°C)
Shipping
Weight
(lb./kg)
M28-0626-GXXX 115 50/60 13.0/13.0 1 5000/6000 125/52 155/70
M52-0626-XXX 230 50/60 6.5/6.5 1 5000/6000 125/52 155/70
M52-0816-032 Stock 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73
M52-0816-XXX 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73
M52-0826-015 Stock 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73
M52-0826-XXX 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73
M52-1016-038 Stock 110/115 50/60 18.9/19.5 1 8300/10000 125/52 165/75
M52-1016-XXX 110/115 50/60 18.9/19.5 1 8300/10000 125/52 165/75
M52-1026-021 Stock 220/230 50/60 9.5/9.8 1 8300/10000 125/52 165/75
M52-1026-XXX 220/230 50/60 9.5/9.8 1 8300/10000 125/52 165/75
M52-1216-017 Stock 110/115 50/60 24.0/23.0 1 10000/12000* 125/52 175/79
M52-1216-XXX 110/115 50/60 24.0/23.0 1 10000/12000* 125/52 175/79
M52-1226-034 Stock 220/230 50/60 12.2/11.6 1 10000/12000* 125/52 175/79
M52-1226-XXX 220/230 50/60 12.2/11.6 1 10000/12000* 125/52 175/79
-XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specic model numbers.
* Based on return air temperature slightly above ambient.
M52 Dimensional Drawing
STANDARD CONDENSATE
DRAIN LOCATION
CLEANABLE,
REUSABLE,
ALUMINUM INLET
FILTER LOCATED
BEHIND GRILLE
OPTIONAL
AMBIENT AIR
OUT FRONT
REMOVABLE
“EZ” MOUNT
BRACKET
ENCLOSURE
AIR IN
AMBIENT
AIR OUT
AMBIENT
AIR IN
COOL
AIR
OUT
SERVICE
CORD
PLENIUM AREA
RECESSED 1.44
FRONT
TOP
SIDE
BOTTOM
BACK