INSTRUCTION MANUAL Genesis™ Air Conditioner All Models Protecting Electronics. Exceeding Expectations.™ Pentair Technical Products 2100 Hoffman Way Minneapolis MN 55303 USA +1.763.323.8200 +1.763.576.3200 PentairTechnicalProducts.com Rev.
TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER.......................................................................................................................................................................................3 HANDLING AND TESTING THE AIR CONDITIONER..........................................................................................................................................................3 INSTALLATION INSTRUCTIONS...........................................................
NOTE: Some of the information in this manual may not apply if a special unit was ordered. If additional drawings for a special unit are necessary, they have been inserted. Contact Pentair Technical Products if further information is required. RECEIVING THE AIR CONDITIONER Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents, scratches, loose assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill.
INSTALLATION INSTRUCTIONS 1. Inspect air conditioner. Verify functionality before mounting the air conditioner, seeHANDLING AND TESTING THE AIR CONDITIONER on page 3. 2. Using the cutout dimensions shown in this manual or the cutout template printed on the units shipping carton, prepare the air “IN” and air “OUT” openings, and mounting bolt hole pattern for the enclosure. 3. Using the gasket kit provided, install gaskets to air conditioner. See gasket kit illustration in this manual for proper location. 4.
M13 Design Data Model M13-0116-G1014 Availability Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) 115 50/60 4.0/4.0 1 800/1000 125/52 48/22 115 50/60 4.0/4.0 1 800/1000 125/52 48/22 230 50/60 2.2/2.1 1 800/1000 125/52 48/22 230 50/60 2.2/2.
M13 Components List Part Number Item Number.
M13 Schematic and Wire Diagram, 115/230 Volt 1000 BTU SERVICE CORD TO TEMPERATURE DISPLAY FUSE(S) (OPTIONAL) ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) TEMPERATURE DISPLAY (OPTIONAL) SUPPRESSOR (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY EVAPORATOR BLOWER COMPRESSOR HEATER (OPTIONAL) SUPPRESSOR THERMOSTAT (OPTIONAL) CONDENSER BLOWER WITH OPTIONAL HEAD PRESSURE CONTROL COMPRESSOR RELAY AND OVERLOAD 87976469 THERMOSTAT COMPRESSOR CONDENSER FAN © 2012 Pentair Technical Products EVAPORATOR
M17 Design Data Model M17-0216-G009 Availability Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) Stock 110/115 50/60 6.6/6.7 1 1500/1800 125/52 56/25 110/115 50/60 6.6/6.7 1 1500/1800 125/52 56/25 220/230 50/60 4.2/3.7 1 1500/1800 125/52 56/25 220/230 50/60 4.2/3.
M17 Components List Part Number Item Number.
M17 Schematic and Wire Diagram, 115 Volt 1800 BTU SERVICE CORD FUSE(S) (OPTIONAL) TO TEMPERATURE DISPLAY ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) TEMPERATURE DISPLAY (OPTIONAL) SUPPRESSOR (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY EVAPORATOR BLOWER COMPRESSOR HEATER (OPTIONAL) THERMOSTAT (OPTIONAL) SUPPRESSOR FREEZE THERMOSTAT (OPTIONAL) CONDENSER BLOWER COMPRESSOR FREEZE THERMOSTAT THERMOSTAT COMPRESSOR RELAY AND OVERLOAD CONDENSER FAN EVAPORATOR FAN M17 Schematic and Wire Diagram, 230
M28 Design Data Model Availability Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) M28-0216-G013 STOCK 115 50/60 9.8/9.0 1 2200/2200 125/52 98/45 115 50/60 9.8/9.0 1 2200/2200 125/52 98/45 230 50/60 5.0/4.5 1 2200/2200 125/52 98/45 230 50/60 5.0/4.5 1 2200/2200 125/52 98/45 115 50/60 14.6/14.0 1 3800/4000 125/52 116/53 115 50/60 14.6/14.0 1 3800/4000 125/52 116/53 230 50/60 7.
M28 Mounting Gasket and Cutout Dimensions (3.) Mounting gasket kit 28-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. - 12 - 1. Dashed lines represent air conditioner. 2. Cutout dimensions are for standard unit. 3. Hole may be deleted if service cord is routed through 3.00 x 13.50 cutout (except on units with electric heat).
M28 Components List Part Number (115 Volt) Item Number.
M28 Schematic and Wire Diagram, 115 Volt, 2200 BTU And 230 Volt 6000 BTU SERVICE CORD TO TEMPERATURE DISPLAY FUSE(S) (OPTIONAL) ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) TEMPERATURE DISPLAY (OPTIONAL) SUPPRESSOR (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY EVAPORATOR BLOWER COMPRESSOR HEATER (OPTIONAL) THERMOSTAT (OPTIONAL) COMPRESSOR SUPPRESSOR CONDENSER BLOWER WITH OPTIONAL HEAD PRESSURE CONTROL THERMOSTAT COMPRESSOR RELAY AND OVERLOAD M28 Schematic and Wire Diagram, 230 Volt, 2200 BTU SE
M28 Schematic and Wire Diagram, 115/230 Volt, 4000 BTU & 230 Volt 6000 BTU FUSE(S) (OPTIONAL) SERVICE CORD TO TEMPERATURE DISPLAY ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) SUPPRESSOR (OPTIONAL) RELAY TEMPERATURE DISPLAY (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY EVAPORATOR BLOWER START CAPACITOR COMPRESSOR HEATER (OPTIONAL) THERMOSTAT (OPTIONAL) CONDENSER BLOWER WITH OPTIONAL HEAD PRESSURE CONTROL SUPPRESSOR START CAPACITOR AND RELAY THERMOSTAT COMPRESSOR AND OVERLOAD M28 Schematic a
M33 Design Data Model Availability M33-0416-G010 Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) 115 50/60 13.0/13.2 1 3700/4000 125/52 105/48 115 50/60 13.0/13.2 1 3700/4000 125/52 105/48 230 50/60 7.2/7.3 1 3700/4000 125/52 105/48 230 50/60 7.2/7.
M33 Mounting Gasket and Cutout Dimensions Mounting gasket kit 33-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. 87976469 1. Dashed lines represent aire conditioner. 2. Cutout dimensions for standard unit. 3. Service cord to be routed through 2.00 x 11.12 cutout. 4. Bottom cutout will accomodate air conditioner or heat exchanger.
M33 Components List Part Number (4000 BTU) Item Number 115 Volt 230 Volt Blower, Condenser, Top Discharge 1 38-2019-04 38-2020-04 Blower, Condenser, Front Discharge 1 38-2019-00 38-2020-00 Fan, Evaporator 2 12-1012-01 12-1012-02 Capacitor, Compressor, Start 3 10-1032-13 10-1032-14 Coil, Condenser 4 33-2001-01 33-2001-01 Coil, Evaporator 5 33-2002-02 33-2002-02 Compressor, AK 6 10-1016-26 10-1026-77 Control Panel Assembly, Narrow N/S 10-1106-100 10-1106-100 Filter, Air, Re
M36 Design Data Model Availability M36-0616-G307 Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature 115 50/60 10.0/10.0 1 5000/6000 105/48 115 50/60 10.0/10.0 1 5000/6000 105/48 230 50/60 5.0/5.0 1 5000/6000 105/48 230 50/60 5.0/5.0 1 5000/6000 105/48 Stock M36-0616-GXXX M36-0626-G306 Stock M36-0626-GXXX Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) -XXX will be replaced with a three-digit number designating all desired options.
M36 Mounting Gasket and Cutout Dimensions Mounting gasket kit 36-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. - 20 - 1. Dashed lines represent aire conditioner. 2. Cutout dimensions for standard unit. 3. Service cord to be routed through 3.00 x 14.00 cutout.
M36 Components List Part Number (6000 BTU) Item Number 115 Volt 230 Volt Blower, Condenser 1 38-2019-04 38-2020-04 Blower, Evaporator 2 28-1064-06M 28-1064-05M Capacitor, Compressor, Run 3 52-6032-06 S-6173 Coil, Condenser 4 36-1017-01 36-1017-01 Coil, Evaporator 5 28-1001-01 28-1001-01 Compressor, Rotary 6 10-1016-91 10-1026-123 Control Panel Assembly, Wide N/S 10-1106-101 10-1106-101 Filter, Air, Reusable, Wide N/S 10-1000-56 10-1000-56 7 52-6028-00 52-6028-00 Grille
M52 Design Data Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) M28-0626-GXXX 115 50/60 13.0/13.0 1 5000/6000 125/52 155/70 M52-0626-XXX 230 50/60 6.5/6.5 1 5000/6000 125/52 155/70 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73 115 50/60 14.5/14.5 1 6700/8000 125/52 160/73 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73 230 50/60 8.0/8.0 1 6700/8000 125/52 160/73 110/115 50/60 18.9/19.
M52 Mounting Gasket and Cutout Dimensions Mounting gasket kit 52-1000-50 included. Apply gasket to the back of the air conditioner before mounting to enclosure. 87976469 1. Dashed lines represent air conditioner. 2. Cutout dimensions for standard unit. 3. Hole may be deleted if service cord is routed through 4.50 x 15.63 cutout (except on units with electric heat).
M52 Components List Part Number (115 Volt) Item Number 6000 BTU 8000 BTU 10000 BTU 12000 BTU Blower, Condenser 1 52-6034-10 52-6034-10 52-6034-10 52-6034-10 Blower, Evaporator 2 52-6075-00 52-6075-00 52-6075-00 52-6034-10 Capacitor, Compressor, Run 3 52-6031-01 52-6032-01 52-6032-01 52-6032-01 Coil, Condenser 4 52-6111-00 52-6111-00 52-6111-00 52-6111-03 Coil, Evaporator 5 28-1001-01 52-6002-02 52-6121-01 52-6121-01 Compressor, AK 6 10-1016-08 10-1016-10 10-1016-12 1
M52 Schematic and Wire Diagram, 115 Volt 10000 and 12000 BTU FUSE(S) (OPTIONAL) TO TEMPERATURE DISPLAY SERVICE CORD ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) SUPPRESSOR (OPTIONAL) TEMPERATURE DISPLAY (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY RUN CAPACITOR EVAPORATOR BLOWER CONTACTOR COMPRESSOR HEATER (OPTIONAL) CONDENSER BLOWER WITH OPTIONAL HEAD PRESSURE CONTROL SUPPRESSOR THERMOSTAT AND CONTACTOR THERMOSTAT RUN CAPACITOR COMPRESSOR COMPRESSOR AND OVERLOAD M52 Schematic and Wire Diag
MHB11 Design Data Model Availability Voltage Hz Full Load Amps Phase BTU/Hr. @ Max Ambient Temperature Max Ambient Temperature (°F/°C) Shipping Weight (lb./kg) MHB11-0216-G306 STOCK 115 50/60 9.7/9.0 1 2200/2200 125/52 90/41 115 50/60 9.7/9.0 1 2200/2200 125/52 90/41 230 50/60 5.5/4.6 1 2200/2200 125/52 90/41 230 50/60 5.5/4.6 1 2200/2200 125/52 90/41 110/115 50/60 14.7/13.6 1 3300/4000 125/52 108/49 110/115 50/60 14.7/13.
MHB11 Mounting Gasket and Cutout Dimensions Mounting gasket kit 11-1000-50 included. Apply gasket to the bottom of the air conditioner before mounting to enclosure. 1. Dashed lines represent air conditioner. 2. Cutout dimensions are for standard unit.
MHB11 Schematic and Wire Diagram, 115 Volt, 2200 BTU And 230 Volt 6000 BTU TO TEMPERATURE DISPLAY FUSE(S) (OPTIONAL) ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) TEMPERATURE DISPLAY (OPTIONAL) SUPPRESSOR (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY EVAPORATOR BLOWER SUPPRESSOR COMPRESSOR HEATER (OPTIONAL) THERMOSTAT (OPTIONAL) THERMOSTAT CONDENSER BLOWER WITH OPTIONAL HEAD PRESSURE CONTROL COMPRESSOR COMPRESSOR RELAY AND OVERLOAD - 28 - SERVICE CORD © 2012 Pentair Technical Products 87976469
MHB11 Schematic and Wire Diagram, 230 Volt, 2200 BTU TO TEMPERATURE DISPLAY FUSE(S) (OPTIONAL) TEMPERATURE DISPLAY (OPTIONAL) ELECTROMAGNETIC INTERFERENCE FILTER (OPTIONAL) SUPPRESSOR (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY EVAPORATOR BLOWER COMPRESSOR HEATER (OPTIONAL) START CAPACITOR SUPPRESSOR THERMOSTAT (OPTIONAL) CONDENSER BLOWER WITH OPTIONAL HEAD PRESSURE CONTROL START CAPACITOR THERMOSTAT COMPRESSOR RELAY COMPRESSOR AND OVERLOAD SERVICE CORD MHB11 Schematic and Wire Diagram, 115/23
TEMPERATURE CONTROL The electromechanical thermostat is factory preset to 75°F/23°C. To change the temperature setting, remove the front cover and screen. Use a standard screwdriver to adjust thermostat. For cooler temperatures turn clockwise, for warmer temperatures turn counterclockwise. PRINCIPLES OF OPERATION If electrical power to the air conditioner is interrupted and reapplied immediately, (within 3 to 5 seconds), the compressor may not restart due to the high back pressure of the compressor.
How To Remove, Clean or Install a New Inlet Air Filter RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding capacity and a minimum amount of resistance to air flow. Because they are constructed entirely of aluminum they are lightweight and easy to service. Optimum filter performance is maintained by recoating the filters after washing with RP Super Filter Coat adhesive.
TROUBLE SHOOTING Basic Air Conditioning Trouble Shooting Check List 1. Check manufacturer’s nameplate located on the unit for correct power supply. 2. Turn on power to the unit. The evaporator (Enclosure or “COLD” air) blower should come on. Is there airflow? YES, proceed to step 3. NO, possible problem: • • • Open motor winding Stuck blower motor Obstructed blades Repair or Replace defective part 3. Check thermostat setting and adjust thermostat to the lowest setting.
Symptoms and Possible Causes: SYMPTOM POSSIBLE CAUSE Impellers/blowers not running Unit won’t cool Compressor not running Compressor runs, but has bad valves Loss of refrigerant Low line voltage at start. Should be +/-10% rated voltage.
WARRANTY Pentair Technical Products warrants that the Goods manufactured by Pentair Technical Products will be free from defects in material and workmanship for a period of one (1) year from the date of shipment by Pentair Technical Products, subject to the following conditions and exclusions: C. Conditions. All Goods must be installed and operated according to the following specifications: 1. Maximum voltage variation no greater than plus or minus 10% of nameplate nominal rating; 2.
1. 2. 3. 4. B. C. D. E. F. G. Complete Model Number, Serial Number and description of damaged unit being returned. Original Buyer Purchase Order number and date product was received by Buyer. Quantity to be returned and a brief description of failure for each unit, if different.
Protecting Electronics. Exceeding Expectations.™ Pentair Technical Products 2100 Hoffman Way Minneapolis MN 55303 USA +1.763.323.8200 +1.763.576.3200 PentairTechnicalProducts.com Rev.