Install Instructions

Troubleshooting
MAINTENANCE
SCHEDULE:
Inspect probe annually or more frequently for scale build-up and clean or replace if necessary.
Make certain there is no scale or build-up on the probe or its white Teflon
®
insulator. Be careful not to damage
the Teflon
®
insulator.
Replace probe every 10 years. More frequent replacement of the probe is required if it is used in locales
where significant water treatment is required, or in applications with high make-up water requirements.
Replace the control unit every 15 years.
If control fails to operate as required, perform the following diagnostic checks:
1. Check to be sure that the water level in the boiler is below the level of the probe.
2. Re-check all wiring to ensure proper connections as specified in boiler manufacturer’s wiring diagrams
or these instructions.
3. Check to ensure that Teflon
®
tape has not been used on the threaded connection of the remote sensor
to the boiler.
4. Re-check the electrical ground connection for the remote sensor and control unit.
Replace Probe if:
Teflon
®
insulator is cracked or worn.
Probe is loose.
Failure to follow this caution could cause property damage, personal injury or death.
CAUTION
!
Clean probe by wiping with non-abrasive cloth and rinsing with clean water. DO NOT
use sharp instruments to remove any accumulations of rust or scale.
NOTE