Install Instructions

4
c . I n s e r t the remote sensor (B) into the boiler
tapping (M) as determined in Step 1.
d . Using the adjustable wrench (N), tighten the
b rass hex adapter (P) on the remote sensor
(B) to approximately 63 ft•lb (85 N•m). D O
N OT TIGHTEN BY TURNING THE SENSOR
H O U S I N G .
a . Cut the probe to desired length. S c r ew, clock-
w i s e , the threaded stainless steel probe ex t e n-
sion (A) into the remote sensor (B). C a r e f u l l y
tighten the locking nut to approximately 1 ft•lb
(1.7 N•m). Do not cut the clear plastic protec-
t i ve tube.
STEP 2 - Installing the Remote Sensor
For All Remote Sensors
For the Model RS-1-BR-1 sensors , o n ly :
a . R e m o ve the sensor housing cover (Q).
1 . For Model RS-1-BR-1, using a flathead
s c r ew d ri ver (R), remove the four (4) screws
and separate the housing cover (Q) from the
sensor (B).
2 . For Model RS-1-LP, using a flathead screw -
d ri ver or nut dri ver (R), loosen the two (2)
s c r ews and separate the housing cover (Q)
from the sensor (B).
Model RS-1-BR-1
Model RS-1-LP
OR
b. Apply a small amount of pipe dope to the first
threads (L) of the remote sensor.
I M P O RTA N T : Do not use Teflon
®
tape or thread
sealant.