Install Instructions
Determine where to install the remote sensor based on the following requirements:
a. The tip of the probe or
extension must be installed
above the minimum safe
water level, as determined by
the boiler manufacturer.
b. Probes must be installed ver-
tically if they are more than 5"
(127mm) long.
c. There must be a minimum 1/4"
(6.4mm) clearance between
the probe and any grounding
surface inside the boiler.
STEP 1 - Where to Install the Remote Sensors
3
IMPORTANT: Remote sensors MUST
be installed in a tapping on the boiler.
Sensor Boiler Sensor Sensor Pressure Sensor Temp.
Catalog No. Part No. Tapping Housing Rating (psig) Rating °F
RS-1-LP 176203 3/4" NPT NEMA 1 160 (water)/15 (steam) 250°
RS-1-BR-1* 179524 1" NPT NEMA 4X 250 (water & steam) 406°
* Requires probe extension (See table 3).
Catalog No. Part No. Length, Inches
RS-1/3-SS 176208 4-1/2
PS-1-SS 179530 12
G-2-SS 179156 24
G-3-SS 179157 36
* To be used with remote sensor (RS-1-BR-1)
mounted in ve r tical position only.
Table 2. Remote Sensors
Table 3. Stainless Steel Probe Extensions*