Product Overview

Boiler Controls
McDonnell & Miller
Low Water Cut-Offs Electronic
For Hot Water and Steam Boilers
Series 750
•For commercial or industrial applications
•Primary or secondary control on hot water boilers
Secondary control (manual reset models only) on
steam boilers
•Manual reset models meet the requirements of
ASME Standard CSD-1. If the control is in a low
water condition when there is an interruption of power,
the control will remain in a low water condition when
power is restored. The reset button will need to be
pressed when the water level is restored to a level
above the probe to allow the burner to fire.
Standard Features
•Green power in on indicating LED
Red low water indicating LED
•Test button
No lock out with loss of power if probe is in water
20,000 ohms sensitivity
Series 750
Control Unit
AB CD
6
3
8 (162) 5
1
8 (130) 2
9
16 (65)
3
4 (20)
Dimensions, in. (mm)
Ordering Information
Model Part Weight
Number Number Description lbs. (kg)
750-T-24 176294 LWCO - 24V Auto Reset 2(.9)
750-MT-24 176293 LWCO - 24V Manual Reset 2(.9)
750-T-120 176206 LWCO - 120V Auto Reset 2(.9)
750-MT-120 176207 LWCO - 120V Manual Reset 2(.9)
Electrical Ratings
A
B
C
D
Model
750-T-24
750-MT-24
750-T-120
750-MT-120
Control
Voltage
24VAC
120VAC
Switch Contact Rating
(Pilot Duty)
50VA@24VAC
Or
125VA@120VAC
Control Unit
Temperature Ratings:
Storage: -40˚F to 135˚F (-40˚C to 57˚C)
Ambient: 32˚F to 135˚F (0˚C to 57˚C)
Humidity: 85% (non-condensing)
Electrical Enclosure Rating: NEMA 1 General Purpose
Hz: 50/60
Control Power Consumption: 3 VA (max.)
ITT
8200 N. Austin Ave.
Morton Grove, IL 60053
Phone (847)966-3700
Facsimile (847)966-9052
www.mcdonnellmiller.com
(Remote sensor and probe rod must be ordered separately)