Submittal Sheet

A
B
C
D
EFGHJKLM N P
NPT NPT NPT NPT NPT
1
5
32 (29.3) 3
13
32 (186.5)
3
8
3
8
3
4 2
13
16 (71) 5
3
8 (137) 2
1
2
1
4 2
3
64 (51.9) 3
5
8 (92) 8
5
32 (207) 9
11
16 (246.6) 5
1
2 (140)
For residential and commercial low pressure boiler
applications
For boilers of any steaming capacity
•2
1
2" NPT body tapping for side mounting on boilers
Lever-operated, full port ball valve for easy blow down
Adjustable BX outlet for easy installation
Dual precision switches for dependable operation of the
low water cut-off and alarm or electric water feeder
Large float chamber
Maximum steam pressure 20 psi (1.4 kg/cm
2
)
Series 767
Series 767
Low Water Cut-Offs
Dimensions, in. (mm)
N
E
D
C
J
A
B
K
M
L
G
P
F
H
(
Max. Swing)
Low Water Cut-Offs – Mechanical
For Steam Boilers
®
®
Ordering Information
Model
Part
Weight
Number Number Description lbs. (kg)
767 153700 Low water cut-off 8.5 (3.9)
Electrical Ratings
Motor Switch Rating (Amperes)
Voltage Full Load Locked Rotor Pilot Duty
120 VAC 7.4 44.4
125 VA at 120
240 VAC 3.7 22.2
or 240 VAC
43
Boiler Controls
Boiler Controls
McDonnell & Miller

Summary of content (1 pages)