Warning:
Maintenance and service must be performed by skilled and qualified personnel only.
Replace probe when PFA insulator is cracked or worn or probe is loose.
Test the low water cut-off annually.
Remove and inspect the self-cleaning probe every five years.
Use a non-abrasive cloth and rinse with clean water when the probe requires
cleaning. Do not use sharp instruments to remove accumulations of rust or scale.
Replace probe every ten years.
Replace the low water cut-off control box every 15 years.